Plan Review Notes
Plan Review Notes For Permit 21040258
Permit Number 21040258
Review Stop M
Sequence Number 6
Notes
Date Text
2021-09-20 07:41:296TH REVIEW FBC-2020 MECHANICAL
 PERMIT-21040258
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET AFS-12: THE NEW FIRE RATED ROOM ON THE 4TH
 FLOOR HAVE SEVERAL MECHANICAL DUCTS PENETRATING THE
 RATED WALLS, PLEASE PROVIDE THE CORRECT PROTECTION FOR
 EACH DUCT PENETRATION OF THE RATED WALLS. FBC M 607
  
 2) THE RESPONSE FOR THE MAKE UP AIR FROM ERIK GONZALEZ
 DOES NOT MEET THE CODE. PLEASE PROVIDE MAKE UP AIR PER
 FMC 508.1.1.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  