Plan Review Notes
Plan Review Notes For Permit 21040258
Permit Number 21040258
Review Stop M
Sequence Number 4
Notes
Date Text
2021-07-27 07:39:004TH REVIEW FBC-2020 MECHANICAL
 PERMIT-21040258
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IN REFERENCE TO YOUR RESPONSE TO COMMENT 1 OF THE
 3RD CYCLE REVIEW: THE 2014 FBC M DOES NOT MENTION AN
 INLINE FAN EXCEPT TO SAY THEY SHALL HAVE A CLEAN OUT ON
 BOTH THE INLET AND OUTLET SIDES. THE INLINE FANS BEING
 IN A RATED ROOM IS ONLY REFERENCED IN THE 2020 FBCM. IF
 YOU ARE WANTING TO USE THE 2020 FBC M INSTEAD OF THE
 2014 FBC M THAT THE ORIGINAL PROJECT WAS PERMITTED
 UNDER YOU WILL NEED TO APPLY THE 2020 FBC M TO THE
 ENTIRE DESIGN AND SUBMIT IT AS AN ALTERNATE MEANS AND
 METHOD TO OUR CBO FOR REVIEW.
  
 2) IN REFERENCE TO YOUR RESPONSE TO COMMENTS 2 & 4 OF
 THE 3RD CYCLE REVIEW: AGAIN, THIS CODE SECTION IS NOT
 IN THE 2014 FBC M. SECTION 506.3.11.2 REQUIRES THE
 SURFACE OF THE DUCT SHALL BE CONTINUOUSLY COVERED ON
 ALL SIDES FROM THE POINT AT WHICH THE DUCT ORIGINATES
 TO THE OUTLET TERMINAL. THE SECOND PART OF THIS IS THE
 LOCATION OF THE FANS- 506.5.1.2 IN-LINE FAN LOCATION.
 WHERE ENCLOSED DUCT SYSTEMS ARE CONNECTED TO IN-LINE
 FANS NOT LOCATED OUTDOORS, THE FAN SHALL BE LOCATED IN
 A ROOM OR SPACE HAVING THE SAME FIRE-RESISTANCE RATING
 AS THE DUCT ENCLOSURE. ACCESS SHALL BE PROVIDED FOR
 SERVICING AND CLEANING OF FAN COMPONENTS. SUCH ROOMS OR
 SPACES SHALL BE VENTILATED IN ACCORDANCE WITH THE FAN
 MANUFACTURER?S INSTALLATION INSTRUCTIONS. THESE ARE 2
 SEPARATE SECTIONS, 506.3.11.2 TELLS US THAT THE FIELD
 APPLIED DUCT FIRE WRAP MUST BE CONTINUOUS FROM START TO
 FINISH ON THE GREASE DUCT ONLY. SECTION 506.5.1.2 TELLS
 US ? WHERE ENCLOSED DUCT SYSTEMS ARE CONNECTED TO
 IN-LINE FANS ( WHICH MEANS THE DUCT WRAP IS CONNECTED
 TO THE GREASE DUCT THAT IS CONNECTED TO THE IN-LINE
 FAN) THE FAN SHALL BE LOCATED IN A FIRE-RESISTANT RATED
 ROOM OR SPACE WITH THE SAME RATING AS THE FIELD APPLIED
 FIRE WRAP. SO THE FIRE WRAP MUST INCLUDE ALL OF THE
 GREASE DUCT. SECTION 506.3.11.2 IS ALLOWING THE FAN TO
 BE IN A RATED ROOM OR SPACE AND NOT HAVE TO BE WRAPPED
 ITSELF.
  
  
 3) IN REFERENCE TO YOUR RESPONSE TO COMMENT 5 OF THE
 3RD CYCLE REVIEW: PLEASE SUBMIT THIS REVISION OF THE
 AIR BALANCE SCHEDULE ONCE IT HAS BEEN ADJUSTED. FBC
 107.2.1
  
 4) IN REFERENCE TO YOUR RESPONSE TO COMMENT 6 OF THE
 3RD CYCLE REVIEW: PLEASE SUBMIT THE DOCUMENTATION FOR
 THE MAKE-UP AIR REQUIREMENTS WHEN COMPLETED. FBC
 107.2.1
  
 5) PLEASE PROVIDE THE INLINE FANS SPECIFICATIONS AND
 INSTRUCTION MANUALS. FBC 107.2.1
  
 6) SHEET AFS-12: PLEASE SHOW HOW THE TERMINATION DESIGN
 WILL NOT ALLOW WATER TO BLOW INTO THE HOOD EXHAUST
 DUCT. FBC 107.2.1
  
 7) PLEASE UNDERSTAND THAT THE FIELD APPLIED GREASE DUCT
 ENCLOSURE MUST BE INSTALLED PER FBC M 506.3.11.2, THE
 LISTING OF THE PRODUCT AND THE MANUFACTURE?S
 INSTRUCTIONS. YOU CANNOT STOP THE FIELD APPLIED DUCT
 WRAP AT THE FLOOR OF THE 4TH FLOOR AND THEN START IT
 AGAIN AT THE CEILING OF THE 4TH FLOOR. YOU ARE LEAVING
 THE GREASE DUCT EXPOSED WHICH GOES AGAINST THE FBC M
 506.3.11.2.
  
 8) SHEET M-5.0.07: PLEASE SHOW THE REQUIRED PROTECTION
 OF THE PENETRATIONS IN THE NEW FIRE RATED WALLS IN THE
 4TH FLOOR MECHANICAL ROOM AT ALL DUCT PENETRATIONS. FBC
 M 607
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  