Plan Review Notes
Plan Review Notes For Permit 21040258
Permit Number 21040258
Review Stop M
Sequence Number 3
Notes
Date Text
2021-07-08 14:01:563RD REVIEW FBC-2020 MECHANICAL
 PERMIT-21040258
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) AFTER DOING SO MORE RESEARCH I HAVE DISCOVERED THAT
 THIS PROJECT WAS PERMITTED UNDER THE 2014 FBC M, PLEASE
 FOLLOW THIS EDITION OF OUR MECHANICAL CODE AND ALL
 REFERENCES MUST BE FOR THE 2014 FBC M.
  
 2) THE PIZZA OVEN HAS A TYPE I HOOD INSTALLED ABOVE IT.
 ACCORDING TO SHEET A-1.2.01 OF THE ORIGINAL APPROVED
 PLANS FOR THIS PROJECT THE WALL SEPARATING THE KITCHEN
 FROM THE MANICURE/PEDICURE AREA IS A 2 HOUR RATED WALL.
 THE GREASE DUCT FROM THE TYPE I HOOD AT THE PIZZA OVEN
 IS PENETRATING THIS 2 HOUR WALL, PLEASE SHOW HOW YOU
 WILL PROTECT THE OPENING. FBC M 506.3.11
  
 3) THE 3 OTHER GREASE DUCTS FOR THE KITCHEN HOODS ARE
 PENETRATING THE 2 HOUR RATED WALL SEPARATING THE
 KITCHEN FROM THE HSKP SHOWN ON A-1.2.01. PLEASE SHOW
 HOW YOU WILL PROTECT THE OPENING. FBC M 506.3.11
  
 4) ALL GREASE DUCT THAT HAS FIELD APPLIED GREASE SHALL
 MEET FBC M 506.3.11.2
  
 506.3.11.2 FIELD-APPLIED GREASE DUCT ENCLOSURE.
 COMMERCIAL KITCHEN GREASE DUCTS CONSTRUCTED IN
 ACCORDANCE WITH SECTION 506.3.1 SHALL BE ENCLOSED BY
 FIELD APPLIED GREASE DUCT ENCLOSURE THAT IS A LISTED
 AND LABELED MATERIAL, SYSTEM, PRODUCT, OR METHOD OF
 CONSTRUCTION SPECIFICALLY EVALUATED FOR SUCH PURPOSE IN
 ACCORDANCE WITH ASTM E 2336.
 THE SURFACE OF THE DUCT SHALL BE CONTINUOUSLY COVERED
 ON ALL SIDES FROM THE POINT AT WHICH THE DUCT
 ORIGINATES TO THE OUTLET TERMINAL. DUCT PENETRATIONS
 SHALL BE PROTECTED WITH A THROUGH-PENETRATION FIRE-STOP
 SYSTEM CLASSIFIED IN ACCORDANCE WITH ASTM E 814 OR UL
 1497 AND HAVING A ?F? AND ?T? RATING EQUAL TO THE
 FIRE-RESISTANCE RATING OF THE ASSEMBLY BEING
 PENETRATED. SUCH SYSTEMS SHALL BE INSTALLED IN
 ACCORDANCE WITH THE LISTING AND THE MANUFACTURER?S
 INSTALLATION INSTRUCTIONS. PARTIAL APPLICATION OF A
 FIELD-APPLIED GREASE DUCT ENCLOSURE SYSTEM SHALL NOT BE
 INSTALLED FOR THE SOLE PURPOSE OF REDUCING CLEARANCES
 TO COMBUSTIBLES AT ISOLATED SECTIONS OF GREASE DUCT.
 EXPOSED DUCT-WRAP SYSTEMS SHALL BE PROTECTED WHERE
 SUBJECT TO PHYSICAL DAMAGE.
 5) SHEET M-1.4.02: THE PIZZA HOOD AND THE BATH EXHAUST
 ARE NOT ON THE AIR BALANCE SCHEDULE, PLEASE INCLUDE
 THEM ON AN UPDATED SCHEDULE. FBC 107.2.1
  
 6) PLEASE SHOW THAT THE MAKE UP AIR MEETS THE 10 DEG.
 AIR TEMPERATURE DIFFERENCE FOR THE MAKE UP AIR UNITS.
 FBC M 508.1.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  