| Date |
Text |
| 2021-07-08 14:01:56 | 3RD REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21040258 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) AFTER DOING SO MORE RESEARCH I HAVE DISCOVERED THAT |
| | THIS PROJECT WAS PERMITTED UNDER THE 2014 FBC M, PLEASE |
| | FOLLOW THIS EDITION OF OUR MECHANICAL CODE AND ALL |
| | REFERENCES MUST BE FOR THE 2014 FBC M. |
| | |
| | 2) THE PIZZA OVEN HAS A TYPE I HOOD INSTALLED ABOVE IT. |
| | ACCORDING TO SHEET A-1.2.01 OF THE ORIGINAL APPROVED |
| | PLANS FOR THIS PROJECT THE WALL SEPARATING THE KITCHEN |
| | FROM THE MANICURE/PEDICURE AREA IS A 2 HOUR RATED WALL. |
| | THE GREASE DUCT FROM THE TYPE I HOOD AT THE PIZZA OVEN |
| | IS PENETRATING THIS 2 HOUR WALL, PLEASE SHOW HOW YOU |
| | WILL PROTECT THE OPENING. FBC M 506.3.11 |
| | |
| | 3) THE 3 OTHER GREASE DUCTS FOR THE KITCHEN HOODS ARE |
| | PENETRATING THE 2 HOUR RATED WALL SEPARATING THE |
| | KITCHEN FROM THE HSKP SHOWN ON A-1.2.01. PLEASE SHOW |
| | HOW YOU WILL PROTECT THE OPENING. FBC M 506.3.11 |
| | |
| | 4) ALL GREASE DUCT THAT HAS FIELD APPLIED GREASE SHALL |
| | MEET FBC M 506.3.11.2 |
| | |
| | 506.3.11.2 FIELD-APPLIED GREASE DUCT ENCLOSURE. |
| | COMMERCIAL KITCHEN GREASE DUCTS CONSTRUCTED IN |
| | ACCORDANCE WITH SECTION 506.3.1 SHALL BE ENCLOSED BY |
| | FIELD APPLIED GREASE DUCT ENCLOSURE THAT IS A LISTED |
| | AND LABELED MATERIAL, SYSTEM, PRODUCT, OR METHOD OF |
| | CONSTRUCTION SPECIFICALLY EVALUATED FOR SUCH PURPOSE IN |
| | ACCORDANCE WITH ASTM E 2336. |
| | THE SURFACE OF THE DUCT SHALL BE CONTINUOUSLY COVERED |
| | ON ALL SIDES FROM THE POINT AT WHICH THE DUCT |
| | ORIGINATES TO THE OUTLET TERMINAL. DUCT PENETRATIONS |
| | SHALL BE PROTECTED WITH A THROUGH-PENETRATION FIRE-STOP |
| | SYSTEM CLASSIFIED IN ACCORDANCE WITH ASTM E 814 OR UL |
| | 1497 AND HAVING A ?F? AND ?T? RATING EQUAL TO THE |
| | FIRE-RESISTANCE RATING OF THE ASSEMBLY BEING |
| | PENETRATED. SUCH SYSTEMS SHALL BE INSTALLED IN |
| | ACCORDANCE WITH THE LISTING AND THE MANUFACTURER?S |
| | INSTALLATION INSTRUCTIONS. PARTIAL APPLICATION OF A |
| | FIELD-APPLIED GREASE DUCT ENCLOSURE SYSTEM SHALL NOT BE |
| | INSTALLED FOR THE SOLE PURPOSE OF REDUCING CLEARANCES |
| | TO COMBUSTIBLES AT ISOLATED SECTIONS OF GREASE DUCT. |
| | EXPOSED DUCT-WRAP SYSTEMS SHALL BE PROTECTED WHERE |
| | SUBJECT TO PHYSICAL DAMAGE. |
| | 5) SHEET M-1.4.02: THE PIZZA HOOD AND THE BATH EXHAUST |
| | ARE NOT ON THE AIR BALANCE SCHEDULE, PLEASE INCLUDE |
| | THEM ON AN UPDATED SCHEDULE. FBC 107.2.1 |
| | |
| | 6) PLEASE SHOW THAT THE MAKE UP AIR MEETS THE 10 DEG. |
| | AIR TEMPERATURE DIFFERENCE FOR THE MAKE UP AIR UNITS. |
| | FBC M 508.1.1 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |