| 2021-04-23 10:41:41 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21040258 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET AFS-9 INSTALLATION DETAILS: KEF-4 FAN MUST BE |
| | LOCATED IN A ROOM OR SPACE RATED WITH THE SAME RATING |
| | AS THE DUCT WRAP PROTECTION. THE ROOM OR SPACE MUST BE |
| | VENTILATED PER THE FAN MANUFACTURE?S INSTALLATION |
| | INSTRUCTIONS. FBC M 506.5.1.2 |
| | |
| | 2) PLEASE SHOW DETAILS OF PROPERTY LINES, BUILDINGS AND |
| | OPENINGS INTO BUILDINGS ALONG WITH EXTERIOR WALL |
| | RATINGS WHERE KITCHEN HOOD EXHAUST DUCT TERMINATES |
| | THROUGH THE EXTERIOR WALLS. FBC M 506.3.13.2 & |
| | 506.3.13.3 |
| | |
| | 3) SHEET AFS-12: PLEASE REMOVE STATEMENT ABOUT THE FIRE |
| | WRAP NOT BEING REQUIRED IN THE ROOM. THE FIRE WRAP |
| | SHALL START AT THE HOOD AND END AT THE DUCT TERMINATION |
| | LOCATION AT THE EXTERIOR OF THE BUILDING. FBC M |
| | 506.3.11.2 |
| | |
| | 4) SHEET AFS-12: PLEASE SHOW THE ROOM WITH THE GREASE |
| | DUCT IN-LINE FANS ARE VENTILATED ACCORDING TO THE FAN |
| | MANUFACTURE?S INSTALLATION INSTRUCTIONS. FBC M |
| | 506.5.1.2 |
| | |
| | 5) SHEET AFS-12: PLEASE SHOW PROTECTION AT THE RATED |
| | WALLS WHERE EXHAUST DUCTS PENETRATING THE 2 HR. WALL AT |
| | THE 4TH FLOOR ROOM. |
| | |
| | 6) SHEET AFS-12: PLEASE IDENTIFY THE DUCTWORK AND |
| | LOUVERS INSIDE THE RATED ROOM BESIDE OF THE SHAFT. FBC |
| | 107.2.1 |
| | |
| | 7) PLEASE PROVIDE THE AIR BALANCE SCHEDULE OR REPORT |
| | FOR EACH BUILDING WITH A KITCHEN, IT MUST INCLUDE THE |
| | BATHROOM EXHAUST. FBC M 508.1.2 |
| | |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |