Plan Review Notes
Plan Review Notes For Permit 21040250
Permit Number 21040250
Review Stop B
Sequence Number 1
Notes
Date Text
2021-09-14 08:47:48ROOFING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC RESIDENTIAL WITH WPB
 CHAPTER 1 AMENDMENTS
  
 CORRECTIONS NEEDED -
 1) PLEASE SHOW THE MEAN ROOF HEIGHT. FBC WPB 107.2.1.1
 2) PRODUCT APPROVAL FL5259-R33 THE NUMBER 26 HAS BEEN
 HIGHLITED - #26 HAS A MAX. WIND DESIGN PRESSURE OF
 (-60) - FBC R TABLE R301.2(2) SHOWS A HIGHER PRESSURE
 FOR ROOF WIND ZONE (3R) - PLEASE PROVIDE ADDITIONAL
 BASE SHEET ATTACHMENT DETAILS FROM A DESIGN
 PROFESSIONAL PER NOTE 5.8.3.2 ON THE PRODUCT APPROVAL.
 3) PLEASE CIRCLE THE TILE TO BE USED (LOW, MEDIUM, HIGH
 PROFILE?) IN THE TILE PRODUCT APPROVAL. FBC WPB
 107.2.1.1
  