| 2021-04-26 14:26:30 | 04/27/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THERE IS A GAS WATER TANK TYPE SHOWN ON PLANS AND NO |
| | VENTING SHOWN. PLEASE PROVIDE A DETAIL FOR THE TYPE OF |
| | APPLIANCE THAT WILL BE USED AND ITS VENTING PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 2. THE FROM R 405-202 FLORIDA ENERGY EFFICIENCY HAS AN |
| | ELECTRICAL TANKLESS @ AN EF 0.92, AND THE PLANS SHOW A |
| | TANK TYPE AND THE GAS PLANS IT GIVES THE BTU?S FOR A |
| | TANKLESS, AND, PLEASE CLARIFY AND CORRECT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 3. ON SHEET FS101, THERE IS A DOUBLE DETECTOR CHECK |
| | BACKFLOW. PLEASE NOTE ON PLANS THAT A SEPARATE PERMIT |
| | AND REVIEW IS REQUIRED PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 105.1. |
| | |
| | 4. ON SHEET P101; |
| | A. THERE IS A TANK-TYPE GAS WITH A REFERENCE CODE FOR |
| | 2017, AND SEE COMMENT TWO FOR CLARIFICATION PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | B. DETAIL C-7 SHOWS A SUPPER AND A ROOF DRAIN THAT DOES |
| | NOT APPLY TO THIS STRUCTURE. PLEASE PROVIDE ONE WITH |
| | THE DETAIL FOR THE ONE IN THE BALCONY AREA PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | C. DETAIL B-3 REFERS TO AN ANTI-SCALDING DEVICE THAT IS |
| | NOT REQUIRED FOR RESIDENTIAL APPLICATIONS. THIS MAY BE |
| | OMITTED FROM DRAWING FOR FIELD CLARITY PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | D. ON DETAIL A-2, BEFORE THE METER, YOU HAVE AN NRV. |
| | WHAT IS THIS DEVICE, AND WHAT IS THE PURPOSE. PLEASE |
| | REMOVE OR CLARIFY PER THE WPB AMENDMENTS TO THE FBC |
| | SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 5. ON SHEET P201; |
| | A. HAVE THE BATHROOM GROUP DOWNSTAIRS IN ROOM ONE |
| | ISOLATED FROM THE MAIN TRUCK LINE, AND THE WASHING |
| | CONNECTED TO THE POWDER ROOM ON TWO SEPARATE SYSTEMS |
| | PER THE 2020 FBC R3108.1 HORIZONTAL WET VENT PERMITTED. |
| | |
| | B. PLEASE PROVIDE A SECOND SANITARY RISER DIAGRAM FOR |
| | THE LEFT UNIT PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.3.5.3 (12) RESIDENTIAL PLUMBING. |
| | |
| | 6. THE WASHING MACHINE SHUT OFF VALVES SHALL BE |
| | ACCESSIBLE WITHOUT MOVING OF THE UNITS AND WITHIN REACH |
| | PER THE 2020 FBC SEC. R 2903.9.3. |
| | |
| | 7. THE PIPES UNDER SLAB NEED TO BE INSULATED WITH A |
| | MINIMUM R-3 PER THE 2017 FBC SEC. RE 403.5.3. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |
| | |