| 2021-04-23 14:23:07 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT- 21040185 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE ADDRESS ON THE PERMIT AND ADDRESS ON THE ENERGY |
| | CALCULATIONS DO NOT MATCH. PLEASE PROVIDE THE CORRECT |
| | ADDRESS ON BOTH DOCUMENTS. FBC 107.2.1 |
| | |
| | 2) PLEASE PROVIDE THE ADDRESS FOR THE PROJECT ON THE |
| | MECHANICAL EQUIPMENT SIZING CALCULATIONS. THERE IS NO |
| | ADDRESS ON THE ONE SUBMITTED. FBC 107.2.1 |
| | |
| | 3) PLEASE PROVIDE A MASTER PLAN OF THE COMMUNITY |
| | SHOWING THE TOTAL NUMBER OF R-1 DUPLEX UNITS FOR THIS |
| | COMMUNITY. FBC 107.2.1 |
| | |
| | 4) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS FOR THESE |
| | R-1 OCCUPANCIES BASED ON FBC 403.3.1.1 AND TABLE |
| | 403.3.1.1 FOR TRANSIENT LODGING. |
| | |
| | 5) PLEASE SHOW HOW THE OUTDOOR AIR WILL BE INTRODUCED |
| | INTO EACH UNIT ON THE DRAWINGS. FBC 107.2.1 |
| | |
| | 6) PLEASE PROVIDE A MINIMUM OF 100CFM MAKE UP AIR FOR |
| | THE DRYER CLOSET. FBC M 504.6 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |