| 2021-04-27 15:41:28 | 04/27/21 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. A SUB GAS PERMIT IS REQUIRED BY A LICENSED |
| | CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 105.1. |
| | |
| | 2. PLEASE CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS |
| | OF PIPE PER 2020 FBC RES. SECS. G2413.4.1, G2413.4.2. |
| | |
| | 3. PLEASE PROVIDE THE TYPE OF GAS (LP OR NATURAL) PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | |
| | 4. PLEASE INDICATE THE DELIVERY PRESSURE (PSI) OF THE |
| | SYSTEM ON THE PLAN PER THE 2020 FBC RES. SEC. G2413.2. |
| | |
| | 5. THE HEATER SHOWS 199 CFH, AND THIS IS USUALLY FOR A |
| | TANK-LESS PLEASE CLARIFY AND IF IT IS, PLEASE SEE THE |
| | COMMENT BELOW PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 6. THIS TANK-LESS UNIT CALL FOR A 10.5? WATER COLUMN, |
| | AND THE SERVICE METER DISCHARGES IS A 12? WATER COLUMN |
| | REQUIRING A REGULATOR FOR THIS UNIT AS PER THE |
| | MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER?S |
| | SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS |
| | INSTALLED ON THE BUILDING'S EXTERIOR SHALL BE APPROVED |
| | FOR OUTDOOR INSTALLATION PER THE 2020 FBC RES. SEC. |
| | G2421.1. |
| | |
| | 7. PLEASE SUBMIT THE MANUFACTURER?S SPECIFICATIONS FOR |
| | THE PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | BUILDING'S EXTERIOR SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION PER THE 2020 FBC RES. SEC. G2421.1. |
| | |
| | 8. PLEASE SHOW ALL UNIONS IN FRONT OF REGULATOR 1? OF |
| | EITHER SIDE PER THE 2020 FBC RES. SEC G2421.2. |
| | |
| | 9. PLEASE SHOW DRIP LEG ON GAS HEATER PER THE 2020 FBC |
| | RES. SEC. G2419.2. |
| | |
| | 10. PLEASE SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, |
| | SIZE, TERMINATION POINT, HEIGHT ABOVE THE ROOF, AND |
| | ANCHORING DETAILS OF THE GAS VENT(S) PER THE 2020 FBC |
| | RES. SECS. G2426 THRU G2429.1. |
| | |
| | 11. PLEASE SHOW THAT THE SHUTOFF VALVE WILL BE |
| | ACCESSIBLE WITHOUT MOVING THE APPLIANCE PER THE 2020 |
| | FBC RES. SEC. G2420.5. |
| | |
| | 12. PLEASE PROVIDE VENTING DIAGRAMS SHOWING THE TYPE |
| | AND SIZE OF GAS VENTS, GAS VENT RUNS, AND TERMINATION |
| | LOCATIONS- SECTION 503 FBC FG. |
| | |
| | 13. PLEASE SUBMIT CALCULATIONS FOR COMBUSTION AIR PER |
| | THE 2020 FBC RES. SEC. G2407.1 AND G2439.4 (CLOTHES |
| | DRYERS). SHOW THE LOCATION OF THE METAL LOUVERS THAT |
| | ARE BEING INSTALLED FOR THE COMBUSTION AIR. IF USING |
| | LOUVERS, THEY CANNOT BE LOCATED ON AN EXTERIOR WALL |
| | THAT IS FIRE RATED AS THE FIRE RATING OF THE WALL MUST |
| | BE MAINTAINED PER THE WPB AMENDMENTS TO FBC |
| | SEC.107.2.1. |
| | |
| | 14. PLEASE SHOW THE SIZE OF THE LOUVER(S) ON THE PLANS |
| | PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 15. PLEASE SUBMIT MANUFACTURER?S SPECIFICATION |
| | SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH 2020 FBC RES. SEC. G2408.1. |
| | |
| | 16. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE |
| | INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT |
| | SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE 2020 |
| | FBC RES. SEC. G2413.2 AND G2404.3. |
| | |
| | 17. THE GAS TABLES USED TO REFERENCE THE PLUMBING CODE, |
| | PLEASE PROVIDE UNDER CODES, THE YEAR, GAS REFERENCED |
| | USED PER THE WPB AMENDMENTS TO THE FBC SEC. 101.4 |
| | REFERENCED CODES. |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |
| | |