| 2021-04-23 10:05:12 | CODES IN EFFECT |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020 |
| | 7TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | REVIEW STATUS: FAILED. PLEASE SEE COMMENTS BELOW: |
| | |
| | 1) SHEET E101 GENERAL NOTE #24: NEW ENERGY CODE (2020 |
| | 7TH EDITION) REQUIRES THAT: |
| | |
| | "R 404.1 NOT LESS THAN 90 PERCENT OF THE LAMPS IN |
| | PERMANENTLY INSTALLED LUMINAIRES SHALL HAVE AN EFFICACY |
| | OF AT LEAST 45 LUMENS-PER-WATT OR SHALL UTILIZE LAMPS |
| | WITH AN EFFICACY OF NOT LESS THAN 65 LUMENS-PER-WATT." |
| | |
| | PLEASE UPDATE NOTE 24 TO REFLECT NEW ENERGY CODE |
| | REQUIREMENTS |
| | |
| | 2) SMOKE DETECTORS/CARBON MONOXIDE ALARMS REQUIRED AS |
| | PER FBC R314, R315. PLEASE SHOW LOCATION ON DRAWINGS. |
| | |
| | 3) PLEASE PROVIDE AVAILABLE SHORT CIRCUIT CURRENT AT |
| | ELECTRICAL PANELS FBC 107 |
| | |
| | 4) PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A |
| | NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14 |
| | |
| | ENRIQUE QUINONEZ P.E. |
| | ELECTRICAL PLANS EXAMINER |
| | DEVELOPMENT SERVICES |
| | CITY OF WEST PAM BEACH |
| | 401 CLEMATIS STREET, 1ST FLOOR |
| | WEST PALM BEACH, FL 33401 |
| | |
| | FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS, |
| | 561-805-6746. |
| | |