2021-04-10 08:40:34ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) I DON'T KNOW WHAT WAS EXISTING FOR ELECTRICAL ON
 ORIGINAL PLANS IT ONLY SHOWED FANS, PLEASE SHOW WHAT
 WAS NEW FROM THE ORIGINAL PLAN.
  
 2) RISER IS NOT CLEAR APARTMENT ABOVE GARAGE SHOWS 60A
 PANEL THAT IS NOT SHOWN ON RISER.
  
 3) GARAGE SHOWS A SMOKE AND CARBON MONOXIDE ALARM
 PLEASE SHOW LISTING FOR USE IN A GARAGE.
  
 4) NO CARBON MONOXIDE ALARM SHOWN ON THE SECOND FLOOR
 APARTMENT.
  
 5) FROM ORIGINAL PLAN UNTIL THIS REVISION I DO NOT SEE
 AN ADDED VALUE OF WORK TO ANY OF THESE REVISIONS?