| Plan Review Notes For Permit 21040129 |
| Permit Number |
21040129 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-04-10 08:40:34 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) I DON'T KNOW WHAT WAS EXISTING FOR ELECTRICAL ON | | | ORIGINAL PLANS IT ONLY SHOWED FANS, PLEASE SHOW WHAT | | | WAS NEW FROM THE ORIGINAL PLAN. | | | | | | 2) RISER IS NOT CLEAR APARTMENT ABOVE GARAGE SHOWS 60A | | | PANEL THAT IS NOT SHOWN ON RISER. | | | | | | 3) GARAGE SHOWS A SMOKE AND CARBON MONOXIDE ALARM | | | PLEASE SHOW LISTING FOR USE IN A GARAGE. | | | | | | 4) NO CARBON MONOXIDE ALARM SHOWN ON THE SECOND FLOOR | | | APARTMENT. | | | | | | 5) FROM ORIGINAL PLAN UNTIL THIS REVISION I DO NOT SEE | | | AN ADDED VALUE OF WORK TO ANY OF THESE REVISIONS? |
|