| Plan Review Notes For Permit 21040089 |
| Permit Number |
21040089 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-06-04 13:56:21 | JONATHAN BROOKS JR. | | | BUILDING PLANS EXAMINER | | | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM | | | PHONE (561) 805-6656 | | | EMAIL: [email protected] | | | | | | 1ST REVIEW: FBC 2020 7TH EDITION | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT | | | CITY HALL, OR EMAIL [email protected] AND REQUEST | | | THAT IT BE CONVERTED TO PROJECTDOX. | | | | | | 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT | | | APPROVAL FL16709-R7 SELECTED OPTION FOR SYSTEM NO W-2; | | | EXPOSURE (B); ENCLOSURE (ENCLOSED); ROOF HEIGHT (H<15); | | | ULTIMATE WIND SPEED (180), IS NOT CORRECT. THE CORRECT | | | EXPOSURE FOR THE LISTED ADDRESS IS EXPOSURE C. PLEASE | | | SELECT THE CORRECT OPTIONS. YOU MAY WANT TO USE; SYSTEM | | | NO W-3; EXPOSURE (C); ENCLOSURE (ENCLOSED); ROOF HEIGHT | | | (H<15); ULTIMATE WIND SPEED (180). | | | |
|