| 2021-05-12 13:21:54 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21040041 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M-1: SF-1 MUST MEET FBC M 508.1.1 |
| | 508.1.1 MAKEUP AIR TEMPERATURE. THE TEMPERATURE |
| | DIFFERENTIAL BETWEEN MAKEUP AIR AND THE AIR IN THE |
| | CONDITIONED SPACE SHALL NOT EXCEED 10?F (6?C) EXCEPT |
| | WHERE THE ADDED HEATING AND COOLING LOADS OF THE MAKEUP |
| | AIR DO NOT EXCEED THE CAPACITY OF THE HVAC SYSTEM. |
| | |
| | 2) SHEET M-6: PLEASE SHOW ON THE DRAWINGS THAT THE |
| | SUPPLY AIR FOR THE MAKE UP AIR IS A MINIMUM OF 10 FT. |
| | FROM ANY EXHAUST OR PLUMBING VENTS. FBC M 401.4 |
| | |
| | 3) SHEET M-7: IT APPEARS THAT THE DESIGNER IS CALLING |
| | OUT BOTH 1 INCH THICK 22 GA. GALVANIZED STEEL MINERAL |
| | WOOL PANEL TO PROTECT COMBUSTIBLES FROM DUCT AND UL |
| | APPROVED FIRE BARRIER WRAP. ARE BOTH REQUIRED FOR THIS |
| | DESIGN? IF NOT PLEASE REMOVE THE DESIGN NOT USED. FBC |
| | 107.2.1 |
| | |
| | 4) PLEASE PROVIDE VENTING SPECIFICATIONS FOR THE FBM |
| | BAKING MACHINE AND THE SINGLE RACK OVEN. FBC 107.2.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |