Plan Review Notes
Plan Review Notes For Permit 21040037
Permit Number 21040037
Review Stop E
Sequence Number 1
Notes
Date Text
2021-04-08 14:17:07FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 [email protected]
  
 SERVICE AND FEEDER CONDUCTORS ARE TO SMALL WHEN NOT
 FEEDING THE ENTIRE LOAD AS STATED IN 310.15(B)(7)(1,2)
 THE FEEDERS DO NOT SERVE ENTIRE LOAD. 310.15(B)(16)
 SHALL BE USED.
  
 (1) FOR A SERVICE RATED 100 THROUGH 400 A, THE SERVICE
 CONDUCTORS SUPPLYING THE ENTIRE LOAD ASSOCIATED WITH A
 ONE-FAMILY DWELLING, OR THE SERVICE CONDUCTORS
 SUPPLYING THE ENTIRE LOAD ASSOCIATED WITH AN INDIVIDUAL
 DWELLING UNIT IN A TWOFAMILY OR MULTIFAMILY DWELLING,
 SHALL BE PERMITTED TO HAVE AN AMPACITY NOT LESS THAN 83
 PERCENT OF THE SERVICE RATING.
 (2) FOR A FEEDER RATED 100 THROUGH 400 A, THE FEEDER
 CONDUCTORS SUPPLYING THE ENTIRE LOAD ASSOCIATED WITH A
 ONE-FAMILY DWELLING, OR THE FEEDER CONDUCTORS SUPPLYING
 THE ENTIRE LOAD ASSOCIATED WITH AN INDIVIDUAL DWELLING,
 UNIT IN A TWOFAMILY OR MULTIFAMILY DWELLING, SHALL BE
 PERMITTED TO HAVE AN AMPACITY NOT LESS THAN 83 PERCENT
 OF THE FEEDER RATING.
  
 NO ADDED VALUE HAS BEEN INCLUDED FOR THE 400AMPERE
 SERVICE, IRRIGATION PUMP, SAUNA.