| Plan Review Notes For Permit 21040037 |
| Permit Number |
21040037 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-04-08 14:17:07 | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED | | | NFPA 70 2011 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | [email protected] | | | | | | SERVICE AND FEEDER CONDUCTORS ARE TO SMALL WHEN NOT | | | FEEDING THE ENTIRE LOAD AS STATED IN 310.15(B)(7)(1,2) | | | THE FEEDERS DO NOT SERVE ENTIRE LOAD. 310.15(B)(16) | | | SHALL BE USED. | | | | | | (1) FOR A SERVICE RATED 100 THROUGH 400 A, THE SERVICE | | | CONDUCTORS SUPPLYING THE ENTIRE LOAD ASSOCIATED WITH A | | | ONE-FAMILY DWELLING, OR THE SERVICE CONDUCTORS | | | SUPPLYING THE ENTIRE LOAD ASSOCIATED WITH AN INDIVIDUAL | | | DWELLING UNIT IN A TWOFAMILY OR MULTIFAMILY DWELLING, | | | SHALL BE PERMITTED TO HAVE AN AMPACITY NOT LESS THAN 83 | | | PERCENT OF THE SERVICE RATING. | | | (2) FOR A FEEDER RATED 100 THROUGH 400 A, THE FEEDER | | | CONDUCTORS SUPPLYING THE ENTIRE LOAD ASSOCIATED WITH A | | | ONE-FAMILY DWELLING, OR THE FEEDER CONDUCTORS SUPPLYING | | | THE ENTIRE LOAD ASSOCIATED WITH AN INDIVIDUAL DWELLING, | | | UNIT IN A TWOFAMILY OR MULTIFAMILY DWELLING, SHALL BE | | | PERMITTED TO HAVE AN AMPACITY NOT LESS THAN 83 PERCENT | | | OF THE FEEDER RATING. | | | | | | NO ADDED VALUE HAS BEEN INCLUDED FOR THE 400AMPERE | | | SERVICE, IRRIGATION PUMP, SAUNA. |
|