| Plan Review Notes For Permit 21040031 |
| Permit Number |
21040031 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-04-15 10:58:54 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE | | | SINGLE HUNG WINDOWS IS INCOMPLETE. SUBMIT THE FLORIDA | | | PRODUCT APPROVAL COVERSHEET AND THE INSTALLATION | | | INSTRUCTIONS FOR FL#21857. FBC 107.2.1 | | | | | | 2) SPECIFY THE NUMBER OF WINDOWS BEING REPLACED. THE | | | VALUE FOR THE WORK THAT IS SPECIFIED ON THE APPLICATION | | | OF $2400.00 APPEARS TO BE LOW IF MORE THAN 3 OR 4 | | | WINDOWS ARE BEING REPLACED. FBC 107.2.1 & FBC 109.3 | | | | | | 3) SUBMIT A FLOOR PLAN WITH THE ROOMS IDENTIFIED THAT | | | SHOWS THE LOCATIONS, TYPES AND SIZES OF THE WINDOWS | | | THAT WILL BE REPLACED. FBC 107.2.1 | | | | | | 4) SUBMIT A WINDLOAD SCHEDULE FOR COMPONENTS AND | | | CLADDING. FBC-R 301 | | | |
|