| 2021-04-30 08:52:24 | ROOF TOP GENERATOR | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE PROVIDE DETAILS FOR THE REQUIRED GUARD RAIL | | | OR SHOW DETAILS ON THE DRAWINGS THAT A GUARD RAIL IS | | | NOT REQUIRED. FBC 1015.6 MECHANICAL EQUIPMENT, SYSTEMS | | | AND DEVICES. | | | GUARDS SHALL BE PROVIDED WHERE VARIOUS COMPONENTS THAT | | | REQUIRE SERVICE ARE LOCATED WITHIN 10 FEET (3048 MM) OF | | | A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE AND SUCH | | | EDGE OR OPEN SIDE IS LOCATED MORE THAN 30 INCHES (762 | | | MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW. THE GUARD | | | SHALL EXTEND NOT LESS THAN 30 INCHES (762 MM) BEYOND | | | EACH END OF SUCH COMPONENTS. THE GUARD SHALL BE | | | CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A SPHERE 21 | | | INCHES (533 MM) IN DIAMETER. | | | |
|