| Plan Review Notes For Permit 21031651 |
| Permit Number |
21031651 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2021-08-20 14:20:45 | 3RD REVIEW FBC-2020 MECHANICAL | | | PERMIT-21031651 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET 9 OF ( THE MECHANICAL DRAWING CLEARLY | | | INDICATES A NEW 5-TON UNIT AND THE REPLACEMENT OF THE | | | 4-TON UNIT. PROVIDE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS. FBC EC C403.2.1 | | | | | | 2) THIS APPEARS TO BE A CHANGE OF USE FROM BUSINESS TO | | | A-2. THE CHANGE OF USE FROM AN OFFICE TO A | | | RESTAURANT/LOUNGE WOULD REQUIRE A MECHANICAL LOAD | | | CALCULATION AND WOULD REQUIRE AN OUTDOOR AIR | | | CALCULATION FOR THIS NEW USE OF SPACE. I DO NOT SEE A | | | MUA FOR THE HOOD ( NOT REQUIRED ON THIS PERMIT BUT AN | | | OBSERVATION) SO ARE THE AHU?S MAKING UP FOR THE HOOD? | | | FBC 107.2.1 AND FBC M 508 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|