| 2021-07-20 16:06:44 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 2ND REVIEW |
| | |
| | PLUMBING COMMENTS: DENIED |
| | |
| | PROVISO: PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1, |
| | PROVIDE AS A DEFERRED SUBMITTAL MANUFACTURER?S |
| | SPECIFICATION AND INSTALLATION GUIDE FOR THE |
| | MANUFACTURER'S SPEC/INSTALLATION MANUALS FOR WATER |
| | HEATERS. DOCUMENTS SHALL BE SUBMITTED, APPROVED AND ON |
| | SITE PRIOR TO FINAL INSPECTION. PROCEED AT YOUR OWN |
| | RISK. |
| | |
| | 1.SECOND REQUEST: THE CENTERLINE OF THE WATER CLOSET |
| | SHALL BE 16 INCHES MINIMUM TO 18 INCHES MAXIMUM FROM |
| | THE SIDE WALL OR PARTITION PER FBC ACC 604.2 |
| | |
| | 2.SECOND REQUEST: PER FBC 606.5 EXPOSED PIPES AND |
| | SURFACES. EXPOSED WATER SUPPLY & DRAINPIPES UNDER |
| | LAVATORIES AND SINKS SHALL BE INSULATED OR OTHERWISE |
| | CONFIGURED TO PROTECT AGAINST CONTACT. |
| | |
| | 3.SECOND REQUEST: MIRRORS LOCATED ABOVE LAVATORIES OR |
| | COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF |
| | THE REFLECTING SURFACE40 INCHES (1015 MM) MAXIMUM ABOVE |
| | THE FINISH FLOOR OR GROUND |
| | |
| | 4. THERE IS A KITCHEN WHICH INCLUDES A RANGE WITH A |
| | GREASE HOOD, AN APPARENT KITCHEN SINK WITH DISHWASHER. |
| | APPARENTLY, THERE WILL BE FOOD PREP. PER WPB FBC |
| | 107.2.1, PROVIDE A GREASE INTERCEPTOR TO COMPLY WITH |
| | THE REQUIREMENTS OF FBC PL 1003.3.1. PER WPB FBC |
| | 107.2.1, PROVIDE A SPECIFICATION, SCHEDULE, DETAIL AND |
| | CALCULATIONS FOR THE SAME. PLEASE NOTE, PER FBC PL |
| | 1003.3.2, A FOOD WASTE DISPOSER SHALL NOT DISCHARGE TO |
| | A GREASE INTERCEPTOR. |
| | -GREASE INTERCEPTOR IS PROVIDED |
| | -SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE |
| | CALCULATIONS FOR GREASE INTERCEPTOR. |
| | -NEW COMMENT: PER WPB FBC 107.2.1, PROVIDE DETAIL FOR |
| | UNDER GROUND GREASE INTERCEPTOR; CONCRETE PIT W/FOOT |
| | TRAFFIC LID FOR ACCESS? PROVIDE REBAR REINFORCEMENT |
| | DETAILS. |
| | |
| | 5. SECOND REQUEST; PER WPB FBC 107.2.1, SUBMIT FOR |
| | REVIEW MANUFACTURER'S SPEC/INSTALLATION MANUAL FOR |
| | DISHWASHER. APPROVED MANUFACTURER'S SPEC/INSTALLATION |
| | MANUALS SHALL BE ON SITE PRIOR TO INSPECTION. PROVIDE |
| | SCHEDULE FOR THE SAME; ITEM SHALL COMPLY WITH FBC PL |
| | 409.1; INDICATE APPROPRIATE STANDARDS FOR MACHINE. |
| | PROVIDE DETAIL FOR PLUMBING CONNECTIONS; COMPLY WITH |
| | REQUIREMENTS OF FBC PL 409.2, 409.3 AND 409.4 AS IS |
| | APPLICABLE. |
| | -RESPONSE INDICATES SUBMITTAL FOR DISHWASHER WAS |
| | INCLUDED FOR REVIEW. I CANNOT FIND. |
| | |
| | 6. THE PLUMBING PLAN INDICATES THAT THE APPARENT |
| | KITCHEN SINK IN THE KITCHEN IS A SERVICE SINK. THE |
| | INTENT OF THE REQUIRED SERVICE SINK AS REQUIRED IN FBC |
| | PL TABLE 403.1, IS TO PROVIDE A SUITABLE FIXTURE FOR |
| | CUSTODIAL DUTIES/SERVICES. PER WPB FBC 107.2.1. PROVIDE |
| | A DESIGNATED SERVICE SINK THAT WILL MEET THE CRITERIA. |
| | PROVIDE A DETAIL FOR THE SAME. COMPLIED |
| | -NEW COMMENT: THE THREE-COMPARTMENT SINK DISCHARGING TO |
| | THE GREASE INTERCEPTOR THROUGH A FLOOR SINK NEEDS TO BE |
| | DESIGNATED A POT SINK; WPB FBC 107.2.1. THE FLOOR SINK |
| | SHALL BE VENTED WITH AN INDIVIDUAL VENT CONNECTING TO |
| | EXISTING VENT SYSTEM; FBC PL 909.1, 904.1. PROVIDE |
| | INDIRECT WASTE TO FLOOR SINK W/AIR GAP; FBC PL 802.1.7. |
| | -THE DISHWASHER SHALL ALSO DISCHARGE TO THE FLOOR SINK. |
| | PROVIDE INDIRECT WASTE TO FLOOR SINK W/AIR GAP; FBC PL |
| | 802.1.7. |
| | -PER WPB FBC 107.2.1, PROVIDE A DETAIL SHOWING |
| | DISCHARGE OF BOTH TO FLOOR SINK. |
| | -NEW COMMENT: HAND SINK AND NEW MOP SINK SHALL NOT |
| | DISCHARGE TO THE GREASE INTERCEPTOR; FBC PL 1003.2. |
| | -NEW COMMENT: THE MOP SINK SHALL NOT BE WET VENTED BY |
| | THE HAND SINK; FBC PL 912.1. PROVIDE INDIVIDUAL VENT |
| | FOR MOP SINK; FBC 909.1 OR PROVIDE COMMON VENT; FBC PL |
| | 911. SEE RED LINED DRAWING 10-P PLUMBING RISERS. |
| | |
| | 7. SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE FINISH |
| | WALL SCHEDULES FOR TOILET ROOMS AND SERVICE SINK. |
| | COMPLY WITH FBC PL 310.3 AND FBC 1210.2.2. WALLS AND |
| | PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE SINKS, |
| | URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD, |
| | NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS THAN 4 |
| | FEET (1219 MM) ABOVE THE FLOOR, AND EXCEPT FOR |
| | STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS |
| | SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY |
| | MOISTURE. PLEASE NOTE THAT FBC 1210.2.2 STIPULATES THAT |
| | THE MATERIAL BE "HARD." THE INTENT OF THIS SECTION IS |
| | THAT THE SURROUNDING MATERIAL SHOULD NOT BE OF A TYPE |
| | THAT IS EASILY DAMAGED SUCH THAT THE MATERIAL COULD |
| | BECOME ABSORBENT AND THUS, NOT READILY CLEANABLE AND |
| | SANITIZED. PAINTED DRYWALL, EVEN WHERE COATED WITH |
| | HIGHLY DURABLE PAINTS, DOES NOT MEET THE INTENT OF |
| | SECTION 1210.2.2. THE TYPICAL MATERIALS USED FOR THIS |
| | APPLICATION ARE CERAMIC TILE, FIBERGLASS REINFORCED |
| | PLASTIC (FRP) PANELS, PHENOLIC PANELS, LAMINATED |
| | PLASTIC PANELS, PAINTED STEEL AND STAINLESS STEEL. |
| | -RESPONSE: FINISHES ON THE PLAN. I CAN NOT FIND. PER |
| | WPB FBC 107.2.1, PLEASE INDICATE WHICH PLAN SHEET AND |
| | CLOUD THE NOTE(S)/SCHEDULE. PLEASE NOTE, THE ADDED MOP |
| | SINK SHALL ALSO COMPLY WITH FBC PL 310.3 AND FBC |
| | 1210.2.2. |
| | |
| | 8. COMPLIED |
| | |
| | 9. COMPLIED |
| | |
| | 10.SECOND REQUEST; PER WPB FBC 107.2.1, PROVIDE |
| | EQUIPMENT SCHEDULE FOR ACCUMIX TANKLESS WATER HEATER |
| | INDICATING MANUFACTURER, MODEL NUMBER, GPM AND |
| | ELECTRICAL CHARACTERISTICS; PROVIDE DETAIL. IF IT IS |
| | ALSO A WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS |
| | TO ASSE 1070, PROVIDE NOTE. |
| | -NEW COMMENT: DELETE MULTIPLE FIXTURES WATER TEMPERING |
| | DEVICE DETAIL; WPB FBC 107.2.1 |
| | |
| | 11. SEE PROVISO REGARDING DEFERRED SUBMITTALS: PER WPB |
| | FBC 107.2.1, PROVIDE EQUIPMENT SCHEDULE FOR TANK TYPE |
| | WATER HEATER INDICATING MANUFACTURER, MODEL NUMBER, |
| | STORAGE CAPACITY AND ELECTRICAL CHARACTERISTICS. ALL |
| | DRAWINGS/SCHEDULE OF TANK TYPE WATER HEATER STORAGE |
| | CAPACITY SHALL BE CONSISTENT WITH EACH OTHER. |
| | |
| | 12. COMPLIED |
| | |
| | 13.REGARDING NEW WATER HEATER DETAIL |
| | -PER WPB FBC 107.2.1, SPECIFY AND SIZE THE EXPANSION |
| | TANK. |
| | -RELIEF LINE SHALL DISCHARGE FULL SIZE TO PAN THROUGH |
| | AIR GAP OR TO THE EXTERIOR; FBC PL 504.6 |
| | -REMOVE ALL REFERENCES TO RECIRCULATING PUMP |
| | -PROVIDE PAN W/3/4 INCH DRAIN TO EXTERIOR; 504.7 |
| | |
| | 14. COMPLIED |
| | |
| | 15. ORIGINAL REQUEST: PER WPB FBC 107.2.1, PROVIDE |
| | PLUMBING/EQUIPMENT/ FIXTURE SCHEDULE TO INCLUDE NEW AND |
| | REMAINING EXISTING FIXTURES, EQUIPMENT INCLUDING |
| | APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT |
| | CONFORMS TO ASSE 1070 AS REQUIRED BY FBC PL 419.5, |
| | 607.1.2 AND WATER-HAMMER ARRESTORS THAT CONFORM TO ASSE |
| | 1010 AS REQUIRED FOR QUICK-CLOSING VALVES INCLUDING |
| | DISHWASHERS BY FBC PL 604.9. ADDITIONALLY, SHOW |
| | LOCATIONS ON RISER DIAGRAM AND IDENTIFY THE SAME. |
| | -NEW COMMENT: ICE MAKER IS NOTED IN RESPONSE BUT IS NOT |
| | INDICATED ON THE PLANS. PER WPB FBC 107.2.1, PROVIDE |
| | PLUMBING/EQUIPMENT/ FIXTURE SCHEDULE TO INCLUDE NEW AND |
| | REMAINING EXISTING FIXTURES. |
| | -PER WPB FBC 107.2.1, IDENTIFY ICE MAKER ON THE PLANS; |
| | PROVIDE DRAIN AND WATER. PROVIDE BACKFLOW PROTECTION IN |
| | THE COLD WATER SUPPLY PER FBC PL 608.1 AND INDIRECT |
| | WASTE TO A TRAPPED AND VENTED WASTE RECEPTACLE (HUB |
| | DRAIN IS ACCEPTABLE) PER FBC PL 802 (WASTE RECEPTACLE |
| | SHALL BE READILY ACCESSIBLE). ICE MACHINE SHALL NOT |
| | DISCHARGE TO THE GREASE INTERCEPTOR; FBC PL 1003.2. |
| | -WATER HAMMER ARRESTORS FOR DISHWASHER AND ICE MACHINE |
| | ARE NOT NOTED |
| | |
| | 16.PER WPB FBC 107.2.1, PROVIDE SIZE OF EXISTING |
| | INCOMING WATER SERVICE AND SHOW LOCATION, TYPE AND SIZE |
| | OF EXISTING BACKFLOW PREVENTOR FOR WATER SERVICE. |
| | -NEW COMMENT: PER WPB FBC 107.2.1, PROVIDE A DETAIL AND |
| | SPEC FOR NEW BFP. NEW BFP REQUIRES A SEPARATE PERMIT. |
| | |
| | 17.SECOND REQUEST: PER WPB FBC 107.2.1, REVISE NOTE 11 |
| | BY REPLACING THE DESIGNATED M COPPER WITH L AS PER |
| | COPPER & COPPER ALLOY TUBE AND PIPE STANDARDS PUBLISHED |
| | BY THE COPPER DEVELOPMENT ASSOCIATION STATES "SEAMLESS |
| | COPPER WATER TUBE IS MANUFACTURED IN SIZES 1/4 INCH |
| | THROUGH 12 INCH NOMINAL. TYPES K AND L ARE MANUFACTURED |
| | IN DRAWN TEMPER (HARD) 1/4 INCH THROUGH 12 INCH AND |
| | ANNEALED TEMPER (SOFT) COILS 1/4 INCH THROUGH 2 INCH |
| | WHILE TYPE M IS ONLY MANUFACTURED IN DRAWN (HARD) |
| | TEMPER 1/4 INCH THROUGH 12 INCH." |
| | |
| | 18. COMPLIED |
| | |
| | 19. COMPLIED |
| | |
| | 20. COMPLIED |
| | |
| | 21. COMPLIED |
| | |
| | 22. COMPLIED. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| | THURSDAYS |
| | |
| | 21031651 1254 OKEECHOBEE RD |
| | |
| | |