| 2021-05-12 16:30:58 | CHANGE OF OCCUPANCY | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) DRAWING 1 OF 9 FLOOR PLAN SHOWS "PROPOSED OCCUPANCY" | | | AS "B" - PLEASE REMOVE OR CORRECT TO A-2. | | | 2) PLEASE SHOW CEILING HEIGHTS AND BOTTOM OF FALSE BEAM | | | HEIGHTS - FBC 1208.2 | | | 3) PLEASE PROVIDE A WINDOW SCHEDULE SHOWING THE SIZES | | | OF THE EXTERIOR WINDOWS TO BE REPLACED. | | | 4) PLEASE SHOW THE TOILET PAPER DISPENSER LOCATION (7-9 | | | INCHES TO THE CENTER OF THE DISPENSER) FROM THE FACE OF | | | THE TOILET TO COMPLY WITH FBC A604.7 | | | 5) ACCESSIBLE REST ROOM DOOR CANNOT SWING INTO THE | | | FIXTURE CLEAR FLOOR SPACE - SEE EXCEPTION AND SHOW THE | | | REQUIRED FLOOR SPACE FBC A603.2.3 | | | 6) PLEASE PROVIDE COMPLETE MIAMI DADE OR FLORIDA STATE | | | PRODUCT APPROVALS FOR THE NEW EXTERIOR WINDOWS AND | | | DOORS. ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND | | | MARKED APPROVED BY THE DESIGNER OF RECORD. FBC 107.3.4 |
|