| Date |
Text |
| 2021-04-19 21:14:56 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT-21031623 |
| | 4/19/2021 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE SEVENTH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH |
| | EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH |
| | EDITION 2020 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1- PLEASE INDICATE ON THE PLANS IN ALL AREAS THE MOST |
| | CURRENT CODE CYCLE. THE CURRENT CODE CYCLE IS FBC 2020 |
| | 2- ON PLAN PAGE P3 WATER HEATER NOTE: THERMAL EXPANSION |
| | IS REQUIRED PER FBC 2020 SEC.607.3THERMAL EXPANSION |
| | CONTROL. |
| | WHERE A STORAGE WATER HEATER IS SUPPLIED WITH COLD |
| | WATER THAT PASSES THROUGH A CHECK VALVE, PRESSURE |
| | REDUCING VALVE OR BACKFLOW PREVENTER, A THERMAL |
| | EXPANSION CONTROL DEVICE SHALL BE CONNECTED TO THE |
| | WATER HEATER COLD WATER SUPPLY PIPE AT A POINT THAT IS |
| | DOWNSTREAM OF ALL CHECK VALVES, PRESSURE REDUCING |
| | VALVES AND BACKFLOW PREVENTERS. THERMAL EXPANSION |
| | CONTROL DEVICES SHALL BE SIZED IN ACCORDANCE WITH THE |
| | MANUFACTURER?S INSTRUCTIONS AND SHALL BE SIZED SUCH |
| | THAT THE PRESSURE IN THE WATER DISTRIBUTION SYSTEM |
| | SHALL NOT EXCEED THAT REQUIRED BY SECTION 604.8. |
| | 3- IT APPEARS AS THOUGH THE HEAT RECIRCULATION PUMP |
| | WILL BE INSTALLED OUTDOORS? PLEASE INDICATE HOW THE |
| | RECIRCULATION PUMP WILL BE PROTECTED AGAINST THE |
| | OUTDOOR ELEMENTS. |
| | 4- MASTER BATH TUB REQUIRES A CONTROL VALVE BY A WATER |
| | TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE 1070 |
| | OR CSA B125.3, EXCEPT WHERE SUCH PROTECTION IS |
| | OTHERWISE PROVIDED BY A COMBINATION TUB/SHOWER VALVE IN |
| | ACCORDANCE WITH SECTION P2708.4. FBC R 2713.3 BATHTUB |
| | AND WHIRLPOOL BATHTUB VALVES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | ATELYO BELISLE |
| | PLUMBING INSPECTOR / |
| | PLUMBING PLAN REVIEW |
| | AVAILABLE FROM 1:00 PM TO 4:00 PM |
| | [email protected] |
| | 561-805-6695 |
| | |