| 2021-04-22 13:21:30 | 1ST REVIEW FBC-2020 RES. |
| | PERMIT- 21031619 |
| | 4/21/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET A7: PROVIDE A SHOWER PAN DETAIL- SECTIONS |
| | P2709.1 & P2709.2 FBC RES. |
| | |
| | 2) A7: PROVIDE A CLEANOUT AT THE JUNCTION OF THE |
| | BUILDING DRAIN AND SEWER- P3005.2.3 FBC RES. |
| | |
| | 3) A7: SHOW THE LOCATION OF THE SHUTOFF VALVES FOR THE |
| | WASHING MACHINE. THE VALVES SHALL BE IN A LOCATION THAT |
| | CAN BE ACCESSED- SEE SECTION P2903.9.3 FBC RES. AND |
| | DEFINITION OF ACCESS- SECTION 202 FBC P. THE VALVES |
| | CANNOT BE LOCATED BEHIND THE STACKABLE WASHER/DRYER |
| | UNIT. |
| | |
| | 4) A7: THE WATER RISER SHOWS A POTABLE WATER BACKFLOW |
| | PREVENTER. PLEASE PLACE A NOTE TO INDICATE A SEPARATE |
| | PERMIT IS REQUIRED- SECTION 105.1 WPB. A FL. LICENSED |
| | PLUMBING CONTRACTOR SHALL OBTAIN A SEPARATE PERMIT FOR |
| | INSTALLATION OF THE BACKFLOW PREVENTER IN ACCORDANCE |
| | WITH SECTION 105.1 WPB AND SEC. 90-33 WPB CODE OF |
| | ORDINANCES. THE DEVICE SHALL BE TESTED AND CERTIFIED BY |
| | THE WPB UTILITIES DEPARTMENT PRIOR TO FINAL INSPECTION |
| | BY THE BUILDING DEPARTMENT. PLEASE CONTACT THE WPB |
| | UTILITIES CENTRAL OPERATIONS DEPT. AT 561-822-2210 FOR |
| | FURTHER INFORMATION. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |