| Plan Review Notes For Permit 21031619 |
| Permit Number |
21031619 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-05-03 07:54:52 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) ON SHEET A3, THERE IS A WALL ID TAG (6) ON THE FLOOR | | | PLAN, HOWEVER, THERE IS NO WALL TYPE (6) LISTED IN THE | | | LEGEND. PLEASE CLARIFY. FBC AMENDMENTS 107.2.1 | | | 2) ON SHEET A5 THE GUARDRAIL IS SPECIFIED AS 42" HIGH | | | ON THE PLAN AND 36" IN THE DETAIL. PLEASE CLARIFY. FBC | | | AMENDMENTS 107.2.1 | | | 3) SUBMIT THE PRODUCT APPROVAL FOR THE AH160 ROOF TILE | | | ADHESIVE. FAC RULE 61G20 | | | 4) SUBMIT PRODUCT APPROVALS THAT HAVE BEEN VALIDATED OR | | | CERTIFIED AS COMPLYING WITH THE 2020 FBC SEVENTH | | | EDITION. THE PRODUCT APPROVAL FOR THE UNCLIPPED | | | MULLIONS IS THE ONLY ONE THAT IS CERTIFIED TO COPY WITH | | | THE 2020 FBC. FBC AMENDMENTS 107.2.1 & FAC RULE 61G20 | | | 5) HI-LIGHT OR CIRCLE THE SPECIFIC ITEMS, SIZES, DESIGN | | | PRESSURES, DETAILS, ETC. IN THE PRODUCT APPROVALS THAT | | | WILL BE INSTALLED. FBC AMENDMENTS 107.2.1 | | | 6) THE DESIGNER OF RECORD IS REQUIRED TO REVIEW AND | | | APPROVE THE PRODUCT APPROVALS IN WRITING. FBC | | | AMENDMENTS 107.3.4 | | | |
|