| Plan Review Notes For Permit 21031618 |
| Permit Number |
21031618 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-04-14 11:07:50 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) CIRCLE OR HI-LIGHT THE ADHESIVE TYPE AND IT'S | | | MINIMUM ATTACHMENT RESISTANCE ON PAGE 5 OF NOA | | | NO.18-0509.16 FOR THE ROOF TILE. FBC AMENDMENTS 107.2.1 | | | | | | 2) SPECIFY THE MEAN ROOF HEIGHT AND ROOF SLOPE FOR THIS | | | PROJECT. FBC 107.2.1 |
|