| Plan Review Notes For Permit 21031564 |
| Permit Number |
21031564 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2022-01-18 09:38:07 | REVISION CREATING OFFICE FROM WAREHOUSE | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE SHOW THE ACCESSIBLE DETAILS FOR THE RESTROOM | | | - CLEAR FLOOR SPACE FOR FIXTURES, GRAB BAR LOCATIONS, | | | TOILET PAPER HOLDER LOCATIONS, MIRROR LOCATIONS, ETC | | | PER FBC ACCESSIBILITY CHAPTER 6 | | | | | | 2) RESTROOM DOOR DOES NOT HAVE A CLEAR WIDTH OF 32" PER | | | FBC ACCESSIBILITY 404.2.3 CLEAR WIDTH. | | | DOOR OPENINGS SHALL PROVIDE A CLEAR WIDTH OF 32 INCHES | | | (815 MM) MINIMUM. CLEAR OPENINGS OF DOORWAYS WITH | | | SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE OF | | | THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 DEGREES. | | | | | | | | | | | | |
|