| Date |
Text |
| 2021-10-21 09:51:38 | 3RD REVIEW FBC-2017 PLUMBING |
| | PERMIT- 21031564 (REVISION TO 20100237) |
| | 10/21/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET A1: THE ARCHITECT'S RESPONSE LETTER TO 2ND |
| | REVIEW COMMENTS STATE THE OCCUPANCY IS A "PERSONAL |
| | PRIVATE OFFICE FOR THE BUILDING OWNER WHICH HAS A HDCP |
| | BATHROOM IN THE BUILDING LESS THAN 100 FT. AWAY". |
| | PLEASE SHOW THE LOCATION OF THE EXISTING BATHROOM ON |
| | THE PLANS- SECTION 107.2.1 WPB. |
| | |
| | 2) SHEETS A1 & A2: AS NOTE ON SHEET A1 UNDER CODE DATA |
| | THE PRIVATE BATHROOM SHALL BE DESIGNED AND CONSTRUCTED |
| | IN COMPLIANCE WITH THE FBC ACC- 2017. PLEASE ADDRESS |
| | THE FOLLOWING CODE REQUIREMENTS ITEMIZED BELOW AND NOTE |
| | THAT THERE ARE NO EXCEPTIONS IN THE CODES LISTED THAT |
| | EXEMPTS PRIVATE OFFICES. |
| | |
| | A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | WATER CLOSET- SECTION 604.3. |
| | B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | LAVATORY- SECTION 606.2. (NOTE- ITEM 1 EXEMPTS THE KNEE |
| | AND TOE CLEARANCES.) |
| | C) TURNING SPACE DIAGRAM AND DIAMETER- SECTION 304.3. |
| | D) CENTERLINE OF THE WATER CLOSET FROM THE SIDE WALL- |
| | SECTION 604.2. |
| | E) HEIGHT OF THE MIRROR FROM THE FINISHED FLOOR TO THE |
| | REFLECTIVE SURFACE- SECTION 603.3 |
| | F) WATER CLOSET GRAB BAR REINFORCEMENT LOCATIONS BASED |
| | ON SECTIONS 604.5 & 609.4. |
| | G) LOCATION OF THE WATER CLOSET FLUSH CONTROL- SECTION |
| | 604.6. |
| | H) CENTERLINE OF THE TOILET PAPER DISPENSER MEASURED |
| | FROM THE FRONT OF THE WATER CLOSET- SECTION AND FIGURE |
| | 604.7. |
| | I) BASED ON SECTIONS 608.2 THE SHOWER COMPARTMENT SHALL |
| | BE EITHER BE A TRANSFER TYPE DIMENSIONED AT 36X36 |
| | INCHES, OR A STANDARD ROLL-IN TYPE WITH MINIMUM CLEAR |
| | DIMENSIONS OF 30X60 INCHES. |
| | K) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR EITHER |
| | A TRANSFER OR ROLL-IN TYPE SHOWER- SECTIONS 608.2.1 & |
| | 608.2.2.1. |
| | L) SHOWER GRAB BAR REINFORCEMENT LOCATIONS BASED ON |
| | SECTIONS 608.3 AND 609.4. |
| | M) LOCATION OF CONTROL, FAUCET, AND SHOWER SPRAY IN THE |
| | SHOWER- SECTION 608.5.1 OR 608.5.2. |
| | N) HEIGHT OF THE KITCHEN SINK- SECTION 606.3. (THE PLAN |
| | SHOWS 36-INCHES HOWEVER THE CODE DOES NOT PROVIDE AN |
| | EXCEPTION FOR KITCHEN SINKS FROM MEETING THE MAXIMUM |
| | 34-INCHES FROM THE FINISH FLOOR TO THE HIGHER OF THE |
| | RIM OF THE SINK OR COUNTER SURFACE). |
| | O) CLEAR FLOOR SPACE DIAGRAM AND DIMENSION FOR THE |
| | KITCHEN SINK- SECTION 606.2. (ITEM 1 ALLOWS FOR A |
| | PARALLEL APPROACH BECAUSE THERE IS NO COOKTOP OR |
| | RANGE). |
| | |
| | 3) A2: THE PLUMBING SPECIFICATIONS INDICATE A |
| | NON-THERMOSTATIC SHOWER VALVE HOWEVER A |
| | BALANCED-PRESSURE, THERMOSTATIC OR BALANCED |
| | PRESSURE/THERMOSTATIC VALVE SHALL BE INSTALLED- SECTION |
| | 424.3 FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |