| 2021-06-03 11:13:39 | 2ND REVIEW FBC-2017 PLUMBING |
| | PERMIT- 21031564 (REVISION TO 20100237) |
| | 6/3/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE REVISED PLAN INDICATES A CHANGE OF OCCUPANCY |
| | FROM AN S TO A B OCCUPANCY- STORAGE WAREHOUSE TO |
| | PRIVATE OFFICE. BASED ON THE PLAN THIS APPEARS TO BE A |
| | NEW TENANT OCCUPANCY. REFER TO SECTIONS 202, AND 1010.1 |
| | FBC EX AND PROVIDE PLUMBING FIXTURE CALCULATIONS FOR |
| | THE B OCCUPANCY IN ACCORDANCE WITH TABLE 403.1 FBC P. |
| | PLEASE NOTE THAT THE PLAN DOES NOT PROVIDE AN OCCUPANCY |
| | CLASSIFICATION OR OCCUPANT LOAD, HOWEVER IT APPEARS |
| | THAT AT A MINIMUM ONE ACCESSIBLE TOILET ROOM FOR BOTH |
| | MALE AND FEMALE USE WOULD BE REQUIRED PER TABLE 403.1, |
| | AND THE APPLICABLE SUB- SECTIONS UNDER 403. THE |
| | PREVIOUS PLAN INDICATED A NEW TOILET ROOM HOWEVER THE |
| | REQUIRED TOILET ROOM AND REQUIRED FIXTURES HAVE BEEN |
| | ELIMINATED. PLEASE REVISE THE PLAN TO SHOW THE PLUMBING |
| | PIPING AND ACCESSIBILITY DETAILS. |
| | |
| | 2) PLUMBING: |
| | A) SANITARY AND WATER SUPPLY FLOOR PLAN DRAWINGS AND |
| | RISERS. |
| | B) PLUMBING FIXTURE SCHEDULE. |
| | C) REQUIRED HOT WATER SOURCE AND SUPPLY FOR WASHING, |
| | CULINARY PURPOSES, CLEANING ETC. |
| | |
| | 3) ACCESSIBILITY: |
| | A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | WATER CLOSET- SECTION 604.3. |
| | B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | LAVATORY- SECTION 606.2. |
| | C) TURNING SPACE DIAGRAM AND DIAMETER- SECTION 304.3. |
| | D) CENTERLINE OF THE WATER CLOSET FROM THE SIDE WALL- |
| | SECTION 604.2. |
| | E) HEIGHT OF THE WATER CLOSET SEAT FROM THE FINISHED |
| | FLOOR- SECTION 604.4. |
| | F) HEIGHT OF THE MIRROR FROM THE FINISHED FLOOR TO THE |
| | REFLECTIVE SURFACE- SECTION 603.3 |
| | G) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE WATER CLOSET- SECTION 604.5 & 609.4, |
| | FIGURES 604. |
| | H) LOCATION OF THE WATER CLOSET FLUSH CONTROL- SECTION |
| | 604.6. |
| | I) CENTERLINE OF THE TOILET PAPER DISPENSER MEASURED |
| | FROM THE FRONT OF THE WATER CLOSET- SECTION AND FIGURE |
| | 604.7. |
| | K) KNEE AND TOE CLEARANCES FOR THE LAVATORY- SECTION |
| | 606.2. |
| | |
| | 3) THE SUBMITTED ENERGY EFFICIENCY FORM R405 IS USED |
| | FOR RESIDENTIAL OCCUPANCIES. PLEASE PROVIDE THE |
| | APPLICABLE COMPLIANCE DOCUMENT- SECTION C101.5.1 FBC |
| | EC. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |