| Plan Review Notes For Permit 21031564 |
| Permit Number |
21031564 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-06-17 09:43:58 | REVISION CREATING OFFICE FROM WAREHOUSE | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | 1) PLEASE SHOW EXTERIOR WALL FRAMING ATTACHMENTS TO THE | | | EXISTING STRUCTURE TO COMPLY WITH THE WIND LOADS FBC | | | 1609 | | | 2) OCCUPANCY CHANGE FROM WAREHOUSE STORAGE TO OFFICE | | | "B" - THE LANDING AT THE ADDED EXTERIOR DOORS NEEDS TO | | | BE EXTENDED (44" OUT FROM THE DOOR) TO COMPLY WITH FBC | | | 1010.1.6 | | | 3) DOOR PRODUCT APPROVAL INSTALLATION INSTRUCTIONS ARE | | | EXPIRED - PLEASE PROVIDE THE REVISED (02/04/2019) | | | INSTALLATION INSTRUCTIONS FOR THE DOOR. FBC 107 | | | 4) PLEASE PROVIDE THE FLORIDA PRODUCT APPROVAL FRONT | | | PAGES FOR THE SHUTTERS (ONLY THE INSTALLATION | | | INSTRUCTIONS WERE PROVIDED). FBC 107 | | | 5) PLEASE SHOW THE HEIGHT FROM THE FINISHED FLOOR TO | | | THE BOTTOM OF THE CEILING DECK ADDED. FBC 1208.2 | | | 6) PLEASE SHOW THE OCCUPANCY CLASSIFICATION FOR THE | | | ADJOINING SPACE - SEPARATION NEEDS TO COMPLY WITH FBC | | | 508.1 | | | | | | | | | | | | |
|