| 2021-04-22 10:57:55 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT- 21031564 (REVISION TO 20100237) |
| | 4/21/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE SUBMITTED REVISION APPLICATION INDICATES |
| | "ADDITIONAL PLUMBING" HOWEVER NO PLUMBING PLANS AND |
| | DETAILS HAVE BEEN SUBMITTED. IN ACCORDANCE WITH |
| | SECTIONS 107.2.1 & 107.3.5.3.1.3 WPB PLEASE PROVIDE |
| | COMPLETE PLUMBING DEMOLITION AND RE-WORK PLANS |
| | INCLUDING: |
| | A) MINIMUM FIXTURE CALCULATIONS PER TABLE 403.1 FBC P. |
| | PROVIDE A SCHEDULE INDICATING THE NUMBER OF REQUIRED |
| | AND PROVIDED PLUMBING FIXTURES BASED ON THE OCCUPANT |
| | LOAD AND OCCUPANCY CLASSIFICATION OF THE SPACE. |
| | A) PLUMBING FLOOR PLAN SHOWING LOCATIONS OF ALL, NEW OR |
| | REPLACED PLUMBING FIXTURES AND PIPING. |
| | B) SANITARY DRAINAGE AND WATER RISER DRAWINGS. |
| | C) PLUMBING FIXTURE AND DEVICE SCHEDULES. |
| | D) WATER HEATER EQUIPMENT SCHEDULE AND SPECS. |
| | E) PLUMBING PIPING SPECIFICATIONS. |
| | F) SLAB REPAIR DETAIL. |
| | |
| | 2) REFER TO SECTION 1003.3.1 FBC P. A NEW KITCHEN IS |
| | SHOWN ON THE PLAN WHICH MAY REQUIRE INSTALLATION OF A |
| | GREASE INTERCEPTOR TO RECEIVE THE DRAINAGE FROM |
| | PLUMBING FIXTURES DISCHARGING GREASE LADED WASTE. |
| | PLEASE PROVIDE A SCOPE OF WORK FOR COOKING OPERATIONS |
| | IN THE KITCHEN, A KITCHEN EQUIPMENT PLAN, AND |
| | CORRELATING EQUIPMENT SCHEDULE. |
| | |
| | 2) MISSING ACCESSIBILITY DETAILS PER FBC ACC- |
| | A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | WATER CLOSETS- SECTION 604.3. |
| | B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | LAVATORIES- SECTION 606.2. |
| | C) TURNING SPACE DIAMETERS- SECTION 304.3. |
| | D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE |
| | WALLS- SECTION 604.2. |
| | E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED |
| | FLOORS- SECTION 604.4. |
| | F) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO |
| | THE REFLECTIVE SURFACES- SECTION 603.3 |
| | G) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4, |
| | FIGURES 604. |
| | H) LOCATION OF THE WATER CLOSET FLUSH CONTROLS - |
| | SECTION 604.6. |
| | I) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED |
| | FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND |
| | FIGURE 604.7. |
| | K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION |
| | 606.2 |
| | |
| | SHOWER- |
| | L) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | SHOWER- SECTIONS 608.2.1/608.2.2 |
| | M) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE ACCESSIBLE SHOWER- SECTIONS |
| | 608.3.1/608.3.2. |
| | N) LOCATION OF CONTROL, FAUCET, AND SHOWER SPRAY IN THE |
| | SHOWER- SECTION 608.5.1/608.5.2. |
| | 0) SHOWER SPRAY UNIT SPECIFICATIONS PER SECTION 608.6. |
| | P) LOCATION AND INSTALLATION DIMENSIONS FOR AN |
| | ACCESSIBLE SHOWER SEAT (IF INSTALLED)- SECTIONS 610.3. |
| | |
| | DRINKING FOUNTAINS (WHERE REQUIRED AND INSTALLED)- |
| | Q) REFER TO SECTIONS 306, 307, AND 602 FBC ACC AND |
| | PROVIDE DRINKING FOUNTAIN INSTALLATION DETAILS AND |
| | ELEVATION VIEWS SHOWING KNEE AND TOE CLEARANCES, SPOUT |
| | HEIGHTS, AND SPOUT LOCATIONS. SHOW THE REQUIRED 30 X 48 |
| | IN. CLEAR FLOOR SPACE FOR A FORWARD WHEELCHAIR APPROACH |
| | TO THE FOUNTAIN- SECTION 602.2 FBC ACC, AND SHOW HOW |
| | THE LOCATIONS OF THE FOUNTAINS WILL BE IN COMPLIANCE |
| | WITH SECTION 307.2 PROTRUSION LIMITS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |