| 2021-05-25 18:20:23 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21031467 |
| | 5/25/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. COMMENTS FROM THE 1ST |
| | REVIEW LISTED BELOW HAVE BEEN MARKED AS PASSED OR |
| | FAILED. NOTES IN CAPS HAVE BEEN ADDED TO FAILED |
| | COMMENTS FOR FURTHER CLARIFICATION. PLEASE NOTE THAT I |
| | AM AVAILABLE TO DISCUSS ANY OF THE COMMENTS WITH THE |
| | DESIGN PROFESSIONALS AND THE CONTRACTOR TO HELP |
| | EXPEDITE APPROVAL OF THE PLUMBING PLANS. |
| | |
| | 1) FAILED. SHEETS CS-1, A-1 & P-1: CONCERNING TOILET RM |
| | 113 PLEASE REFER TO SECTION 213.2 EXCEPTION-3 AND THE |
| | ADVISORY UNDER THE SECTION- ADVISORY 213.2 TOILET ROOMS |
| | AND BATHING ROOMS EXCEPTIONS 3 AND 4. A "CLUSTER" IS A |
| | GROUP OF TOILET ROOMS PROXIMATE TO ONE ANOTHER. |
| | GENERALLY, TOILET ROOMS IN A CLUSTER ARE WITHIN SIGHT |
| | OF, OR ADJACENT TO, ONE ANOTHER. TOILET RM 113 DOES NOT |
| | MEET THE EXCEPTION AND SHALL BE DESIGNED TO BE |
| | ACCESSIBLE IN ACCORDANCE WITH SECTIONS 213.2 AND 603. |
| | BASED ON TABLE 403.3 AND SECTIONS 403.2 & 403.3 IT |
| | APPEARS THAT A REQUIRED PUBLIC/EMPLOYEE TOILET ROOM HAS |
| | BEEN ELIMINATED. THE PREVIOUS PLAN SHOWED THE |
| | CHILDREN'S SEPARATED BOYS AND GIRLS TOILET ROOMS AND |
| | ALSO TOILET ROOMS- 108 & 113. THE TWO UNISEX TOILET |
| | ROOMS APPEARED TO MEET THE REQUIREMENT FOR SEPARATE |
| | FACILITIES FOR THE PUBLIC AND EMPLOYEES- SECTION 403.3. |
| | AND ALSO MATCHED THE FIXTURE CALCULATION TABLE ON CS-1 |
| | WHICH INDICATED TWO UNISEX TOILET ROOMS. TOILET ROOM |
| | 113 IS NOW CONVERTED INTO CLOSET 113, AND THE PLUMBING |
| | FIXTURE CALCULATIONS ON CS-1 HAVE BEEN REVISED TO SHOW |
| | ONE UNISEX TOILET ROOM. PLEASE REVISE THE PLAN TO SHOW |
| | THE TWO REQUIRED TOILET ROOMS. |
| | |
| | 2) FAILED. SHEETS A-1 & P-1: REFER TO SECTION 403.2 FBC |
| | P AND LABEL TOILET RM 113 AS EITHER MALE OR FEMALE. |
| | REFER TO ABOVE NOTES ON COMMENT #1. SEPARATE FACILTIES |
| | ARE REQUIRED HOWEVER IT IS ACCEPTABLE TO LABEL BOTH |
| | TOILET ROOMS AS UNISEX BASED ON SECTION 403.2.1 FBC P. |
| | PLEASE REVISE THE PLAN TO SHOW THE LOCATIONS OF THE |
| | REQUIRED PUBLIC/EMPLOYEE TOILET ROOMS. |
| | |
| | ***ADVISORY FOR COMMENTS #1 & 2: THE CURRENT PLAN SHOWS |
| | COMPLIANCE FOR THE NUMBER OF REQUIRED ACCESSIBLE |
| | FIXTURES FOR THE BOYS AND GIRLS- TOILET RMS-109 AND |
| | 112. THE FIXTURES IN GIRLS-RM 110 ARE NOT REQUIRED |
| | WHICH PROVIDES AN OPTION OF REDESIGNING THE ROOM TO |
| | MEET THE REQUIREMENT FOR THE MISSING ACCESSIBLE |
| | PUBLIC/EMPLOYEE TOILET ROOM FIXTURES. |
| | |
| | 3) PASSED. SHEETS A-1 & P-1: REFER TO SECTIONS 604.1, |
| | 604.9, AND ADVISORY 604.9 AND SPECIFICATIONS TABLE- |
| | "ADVISORY 604.9 WATER CLOSETS AND TOILET COMPARTMENTS |
| | FOR CHILDREN'S USE. THE REQUIREMENTS IN 604.9 ARE TO BE |
| | FOLLOWED WHERE THE EXCEPTION FOR CHILDREN'S WATER |
| | CLOSETS IN 604.1 IS USED. THE FOLLOWING TABLE PROVIDES |
| | ADDITIONAL GUIDANCE IN APPLYING THE SPECIFICATIONS FOR |
| | WATER CLOSETS FOR CHILDREN ACCORDING TO THE AGE GROUP |
| | SERVED AND REFLECTS THE DIFFERENCES IN THE SIZE, |
| | STATURE, AND REACH RANGES OF CHILDREN AGES 3 THROUGH |
| | 12. THE SPECIFICATIONS CHOSEN SHOULD CORRESPOND TO THE |
| | AGE OF THE PRIMARY USER GROUP. THE SPECIFICATIONS OF |
| | ONE AGE GROUP SHOULD BE APPLIED CONSISTENTLY IN THE |
| | INSTALLATION OF A WATER CLOSET AND RELATED ELEMENTS." |
| | PLEASE REVISE THE FLOOR PLAN AND ELEVATION DRAWINGS ON |
| | A-1 TO SHOW THE AGE DESIGNATION FOR EACH TOILET ROOM. |
| | |
| | 4) PASSED. A-1: PROVIDE THE SPOUT HEIGHT FOR THE HIGH- |
| | STANDING PERSONS DRINKING FOUNTAIN- SECTION 602.7. |
| | REFER TO FIGURE 602.5 AND SHOW SPOUT LOCATIONS. |
| | |
| | 5) PASSED. A-1: REFER TO SECTION AND SHOW HOW THE |
| | LOCATIONS OF THE FOUNTAINS WILL BE IN COMPLIANCE WITH |
| | SECTION 307.2 PROTRUSION LIMITS. |
| | |
| | 6) PASSED. P-1: PROVIDE A PLUMBING FIXTURE SCHEDULE IN |
| | COMPLIANCE WITH SECTION 405 FBC P. |
| | |
| | 7) FAILED. P-1 PLUMBING PLAN AND SANITARY RISER- FBC P: |
| | THE EWC IS NOT LABELED IN THE RISER. |
| | |
| | A) FAILED. THE 1-1/4 IN. TRAP FOR THE URINAL CANNOT BE |
| | APPROVED WITHOUT SUBMITTAL OF URINAL SPECIFICATIONS IN |
| | THE REQUESTED FIXTURE SCHEDULE- TABLE 709.1. THE |
| | COMMENT RESPONSE FROM THE ARCHITECT INDICATES THE |
| | URINAL WILL HAVE A 2 INCH TRAP HOWEVER AN 1-1/4 INCH |
| | TRAP IS SHOWN. |
| | |
| | B) PASSED. SHOW THE REQUIRED CLEANOUT AT THE JUNCTION |
| | OF THE BUILDING DRAIN AND SEWER- SECTION 708.1.3. |
| | |
| | C) PASSED. PROVIDE A VENT FOR THE WATER CLOSET IN 112- |
| | SECTION 901.2.1. |
| | |
| | D) PASSED. PROVIDE AN INDIVIDUAL VENT FOR THE URINAL IN |
| | 112- SECTIONS 911.1 & 912.1. |
| | |
| | E) PASSED. THE WYE FITTING BY THE WATER CLOSET IN GIRLS |
| | 110 IS NOT PROPERLY DIRECTING THE FLOW OF DRAINAGE FROM |
| | THE WATER CLOSET AND THE DRAIN PIPE FROM TOILET RM 113- |
| | SECTION 706.3. |
| | |
| | F) PASSED. PROVIDE THE SIZE OF THE TRAPS AT THE |
| | 3-COMPARTMENT SINK- TABLE 709.1. PLEASE NOTE EACH WELL |
| | OF A MULTIPLE-COMPARTMENT SINK SHALL DISCHARGE |
| | INDEPENDENTLY TO A WASTE RECEPTOR- SECTION 802.1.1. |
| | PROVIDE A DETAIL AND INDICATE WHICH TYPE OF INDIRECT |
| | WASTE RECEPTOR WILL BE INSTALLED AND ADD IT TO THE |
| | FIXTURE SCHEDULE- SECTION 802.4 FBC P. |
| | |
| | 8) FAILED. P1: PLEASE PROVIDE THE SIZES OF ALL SUPPLY |
| | PIPES SHOWN IN THE WATER RISER- TABLE 604.5 FBC P. |
| | PLEASE SHOW A 3/4 INCH SUPPLY LINE TO THE URINAL PER |
| | THE SLOAN 186- XL-1 FLUSHOMETER SPECIFICATIONS. |
| | |
| | 9) PASSED. P1: INDICATE HOW TEMPERED WATER WILL BE |
| | PROVIDE AT THE LAVATORIES- SECTION 419.5 AND 607.2.1 |
| | FBC P. |
| | |
| | 10) PASSED. P1: THE MAXIMUM ALLOWABLE PIPING LENGTH |
| | FROM THE NEAREST SOURCE OF HEATED WATER TO THE |
| | TERMINATION OF THE LAVATORY SUPPLY PIPES SHALL BE IN |
| | ACCORDANCE WITH SECTION C404.5.1 & TABLE C404.5.1 FBC |
| | EC. |
| | |
| | 11) PASSED. P1: PROVIDE AN EQUIPMENT SCHEDULE FOR THE |
| | WATER HEATER INDICATING THE MAKE, MODEL, KW SIZE, AND |
| | EFFICIENCY RATING OF THE UNIT- TABLE C404.2 FBC EC. |
| | SUBMIT MANUFACTURER'S SPECIFICATIONS. |
| | |
| | 12) PASSED. P1: PROVIDE A PIPING DIAGRAM FOR THE WATER |
| | HEATER- SECTION 502.1 FBC P. |
| | |
| | 13) PASSED.P1: SHOW LOCATIONS OF REQUIRED WATER HAMMER |
| | ARRESTORS AND PROVIDE A DEVICE SCHEDULE- SECTION 604.9 |
| | FBC P. |
| | |
| | 14) PASSED. P1: REFER TO TABLE C403.2.10 FBC EC AND |
| | PROVIDE THE THICKNESSES OF THE HOT WATER PIPE |
| | INSULATION. |
| | |
| | NEW COMMENTS BASED ON REVISED PLANS. |
| | |
| | P1 RESTROOM REFERENCE NOTES: PLEASE REMOVE RM 113 |
| | REFERENCES IN THE SCHEDULE. RM 113 HAS BEEN CONVERTED |
| | TO A CLOSET. A) REMOVE OR REVISE NOTE 7 FROM RM 109. B) |
| | NOTE 4 HAS BEEN USED TWICE. C) THE TEXT FOR NOTE 5 IS |
| | NOT PROVIDED. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |