Plan Review Notes
Plan Review Notes For Permit 21031467
Permit Number 21031467
Review Stop P
Sequence Number 1
Notes
Date Text
2021-04-28 13:28:041ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21031467
 4/28/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS CS-1, A-1 & P-1: CONCERNING TOILET RM 113
 PLEASE REFER TO SECTION 213.2 EXCEPTION-3 AND THE
 ADVISORY UNDER THE SECTION- ADVISORY 213.2 TOILET ROOMS
 AND BATHING ROOMS EXCEPTIONS 3 AND 4. A "CLUSTER" IS A
 GROUP OF TOILET ROOMS PROXIMATE TO ONE ANOTHER.
 GENERALLY, TOILET ROOMS IN A CLUSTER ARE WITHIN SIGHT
 OF, OR ADJACENT TO, ONE ANOTHER. TOILET RM 113 DOES NOT
 MEET THE EXCEPTION AND SHALL BE DESIGNED TO BE
 ACCESSIBLE IN ACCORDANCE WITH SECTIONS 213.2 AND 603.
  
 2) SHEETS A-1 & P-1: REFER TO SECTION 403.2 FBC P AND
 LABEL TOILET RM 113 AS EITHER MALE OR FEMALE.
  
 3) SHEETS A-1 & P-1: REFER TO SECTIONS 604.1, 604.9,
 AND ADVISORY 604.9 AND SPECIFICATIONS TABLE- "ADVISORY
 604.9 WATER CLOSETS AND TOILET COMPARTMENTS FOR
 CHILDREN'S USE. THE REQUIREMENTS IN 604.9 ARE TO BE
 FOLLOWED WHERE THE EXCEPTION FOR CHILDREN'S WATER
 CLOSETS IN 604.1 IS USED. THE FOLLOWING TABLE PROVIDES
 ADDITIONAL GUIDANCE IN APPLYING THE SPECIFICATIONS FOR
 WATER CLOSETS FOR CHILDREN ACCORDING TO THE AGE GROUP
 SERVED AND REFLECTS THE DIFFERENCES IN THE SIZE,
 STATURE, AND REACH RANGES OF CHILDREN AGES 3 THROUGH
 12. THE SPECIFICATIONS CHOSEN SHOULD CORRESPOND TO THE
 AGE OF THE PRIMARY USER GROUP. THE SPECIFICATIONS OF
 ONE AGE GROUP SHOULD BE APPLIED CONSISTENTLY IN THE
 INSTALLATION OF A WATER CLOSET AND RELATED ELEMENTS."
 PLEASE REVISE THE FLOOR PLAN AND ELEVATION DRAWINGS ON
 A-1 TO SHOW THE AGE DESIGNATION FOR EACH TOILET ROOM.
  
 4) A-1: PROVIDE THE SPOUT HEIGHT FOR THE HIGH- STANDING
 PERSONS DRINKING FOUNTAIN- SECTION 602.7. REFER TO
 FIGURE 602.5 AND SHOW SPOUT LOCATIONS.
  
 5) A-1: REFER TO SECTION AND SHOW HOW THE LOCATIONS OF
 THE FOUNTAINS WILL BE IN COMPLIANCE WITH SECTION 307.2
 PROTRUSION LIMITS.
  
 6) P-1: PROVIDE A PLUMBING FIXTURE SCHEDULE IN
 COMPLIANCE WITH SECTION 405 FBC P.
  
 7) P-1 PLUMBING PLAN AND SANITARY RISER- FBC P:
 A) THE 1-1/4 IN. TRAP FOR THE URINAL CANNOT BE APPROVED
 WITHOUT SUBMITTAL OF URINAL SPECIFICATIONS IN THE
 REQUESTED FIXTURE SCHEDULE- TABLE 709.1.
 B) SHOW THE REQUIRED CLEANOUT AT THE JUNCTION OF THE
 BUILDING DRAIN AND SEWER- SECTION 708.1.3.
 C) PROVIDE A VENT FOR THE WATER CLOSET IN 112- SECTION
 901.2.1.
 D) PROVIDE AN INDIVIDUAL VENT FOR THE URINAL IN 112-
 SECTIONS 911.1 & 912.1.
 E) THE WYE FITTING BY THE WATER CLOSET IN GIRLS 110 IS
 NOT PROPERLY DIRECTING THE FLOW OF DRAINAGE FROM THE
 WATER CLOSET AND THE DRAIN PIPE FROM TOILET RM 113-
 SECTION 706.3.
 F) PROVIDE THE SIZE OF THE TRAPS AT THE 3-COMPARTMENT
 SINK- TABLE 709.1. PLEASE NOTE EACH WELL OF A
 MULTIPLE-COMPARTMENT SINK SHALL DISCHARGE INDEPENDENTLY
 TO A WASTE RECEPTOR- SECTION 802.1.1. PROVIDE A DETAIL
 AND INDICATE WHICH TYPE OF INDIRECT WASTE RECEPTOR WILL
 BE INSTALLED AND ADD IT TO THE FIXTURE SCHEDULE-
 SECTION 802.4 FBC P.
  
 8) P1: PLEASE PROVIDE THE SIZES OF ALL SUPPLY PIPES
 SHOWN IN THE WATER RISER- TABLE 604.5 FBC P.
  
 9) P1: INDICATE HOW TEMPERED WATER WILL BE PROVIDE AT
 THE LAVATORIES- SECTION 419.5 AND 607.2.1 FBC P.
  
 10) P1: THE MAXIMUM ALLOWABLE PIPING LENGTH FROM THE
 NEAREST SOURCE OF HEATED WATER TO THE TERMINATION OF
 THE LAVATORY SUPPLY PIPES SHALL BE IN ACCORDANCE WITH
 SECTION C404.5.1 & TABLE C404.5.1 FBC EC.
  
 11) P1: PROVIDE AN EQUIPMENT SCHEDULE FOR THE WATER
 HEATER INDICATING THE MAKE, MODEL, KW SIZE, AND
 EFFICIENCY RATING OF THE UNIT- TABLE C404.2 FBC EC.
 SUBMIT MANUFACTURER'S SPECIFICATIONS.
  
 12) P1: PROVIDE A PIPING DIAGRAM FOR THE WATER HEATER-
 SECTION 502.1 FBC P.
  
 13) P1: SHOW LOCATIONS OF REQUIRED WATER HAMMER
 ARRESTORS AND PROVIDE A DEVICE SCHEDULE- SECTION 604.9
 FBC P.
  
 14) P1: REFER TO TABLE C403.2.10 FBC EC AND PROVIDE THE
 THICKNESSES OF THE HOT WATER PIPE INSULATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  