| 2021-04-27 16:36:43 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET A 1 - THERE ARE INDICATIONS OF COORIDORS, BUT |
| | NO DIMENSIONS. |
| | |
| | PER NFPA 101 CHAPTER 14, NEW EDUCATIONAL OCCUPANCIES |
| | |
| | 14.2.3.2.2 EXIT ACCESS CORRIDORS WITH A REQUIRED |
| | CAPACITY OF LESS THAN |
| | 100 PERSONS SHALL HAVE NOT LESS THAN 44 IN. (1120 MM) |
| | OF CLEAR WIDTH. |
| | |
| | PLEASE PROVIDE DETAILS IN COMPLIANCE. |
| | |
| | |
| | 1A) SHEET A 1 - CORRIDOR WALL RATING |
| | |
| | THERE APPEARS A WALL TYPE INDICATED WITH A SQUARE |
| | AROUND AN A BUT NO INDICATION OF TYPE OF THAT IT IS |
| | SMOKE RATED. |
| | |
| | 14.3.6 CORRIDORS. CORRIDORS SHALL BE SEPARATED FROM |
| | OTHER PARTS OF THE |
| | STORY BY WALLS HAVING A 1-HOUR FIRE RESISTANCE RATING |
| | IN ACCORDANCE WITH |
| | SECTION 8.3, UNLESS OTHERWISE PERMITTED BY ONE OF THE |
| | FOLLOWING: |
| | (1) CORRIDOR PROTECTION SHALL NOT BE REQUIRED WHERE ALL |
| | SPACES NORMALLY |
| | SUBJECT TO STUDENT OCCUPANCY HAVE NOT LESS THAN ONE |
| | DOOR OPENING |
| | DIRECTLY TO THE OUTSIDE OR TO AN EXTERIOR EXIT ACCESS |
| | BALCONY OR CORRIDOR |
| | IN ACCORDANCE WITH 7.5.3. |
| | (2) THE FOLLOWING SHALL APPLY TO BUILDINGS PROTECTED |
| | THROUGHOUT BY AN |
| | APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN |
| | ACCORDANCE |
| | WITH SECTION 9.7: |
| | (A) CORRIDOR WALLS SHALL NOT BE REQUIRED TO BE RATED, |
| | PROVIDED THAT |
| | SUCH WALLS FORM SMOKE PARTITIONS IN ACCORDANCE WITH |
| | SECTION 8.4. |
| | (B) THE PROVISIONS OF 8.4.3.5 SHALL NOT APPLY TO |
| | NORMALLY OCCUPIED |
| | CLASSROOMS. |
| | (3) WHERE THE CORRIDOR CEILING IS AN ASSEMBLY HAVING A |
| | 1-HOUR FIRE |
| | RESISTANCE RATING WHERE TESTED AS A WALL, THE CORRIDOR |
| | WALLS SHALL BE |
| | PERMITTED TO TERMINATE AT THE CORRIDOR CEILING. |
| | (4) LAVATORIES SHALL NOT BE REQUIRED TO BE SEPARATED |
| | FROM CORRIDORS, |
| | PROVIDED THAT THEY ARE SEPARATED FROM ALL OTHER SPACES |
| | BY WALLS |
| | HAVING NOT LESS THAN A 1-HOUR FIRE RESISTANCE RATING IN |
| | ACCORDANCE |
| | WITH SECTION 8.3. |
| | (5) LAVATORIES SHALL NOT BE REQUIRED TO BE SEPARATED |
| | FROM CORRIDORS, |
| | PROVIDED THAT BOTH OF THE FOLLOWING CRITERIA ARE MET: |
| | (A) THE BUILDING IS PROTECTED THROUGHOUT BY AN |
| | APPROVED, SUPERVISED |
| | AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH |
| | SECTION 9.7. |
| | (B) THE WALLS SEPARATING THE LAVATORY FROM OTHER ROOMS |
| | FORM SMOKE |
| | PARTITIONS IN ACCORDANCE WITH SECTION 8.4. |
| | |
| | PLEASE PROVIDE DETAILS IS COMPLIANCE |
| | |
| | |
| | |
| | 2) SHEET A 1 - THERE ARE DOORS TO CLASSROOMS THAT HAVE |
| | NO INDICATED HARDWARE. |
| | |
| | |
| | 14.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE |
| | PERMITTED. |
| | |
| | 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED |
| | READILY FROM THE |
| | EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. |
| | |
| | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE |
| | OF A KEY, A TOOL, |
| | OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE |
| | EGRESS SIDE. |
| | |
| | 7.2.1.5.10* A LATCH OR OTHER FASTENING DEVICE ON A DOOR |
| | LEAF SHALL BE |
| | PROVIDED WITH A RELEASING DEVICE THAT HAS AN OBVIOUS |
| | METHOD OF OPERATION |
| | AND THAT IS READILY OPERATED UNDER ALL LIGHTING |
| | CONDITIONS. |
| | ADDITIONAL INFO IF APPLICABLE.... |
| | |
| | 7.2.1.5.10.2 THE RELEASING MECHANISM SHALL OPEN THE |
| | DOOR LEAF WITH NOT |
| | MORE THAN ONE RELEASING OPERATION, UNLESS OTHERWISE |
| | SPECIFIED IN |
| | 7.2.1.5.10.3, 7.2.1.5.10.4, 7.2.1.5.10.6, OR |
| | 7.2.1.5.10.7. |
| | |
| | PLEASE PROVIDE THE EXACT TYPE OF HARDWARE FOR EACH |
| | CLASSROOM DOOR. |
| | |
| | |
| | ADDITIONAL INFO TO PROVIDE IF APPLICABLE.... |
| | |
| | PER NFPA 101, CH 14 |
| | |
| | 14.2.2.2.4* CLASSROOM DOOR LOCKING TO PREVENT UNWANTED |
| | ENTRY. |
| | (1) THE LOCKING MEANS SHALL BE CAPABLE OF BEING ENGAGED |
| | WITHOUT |
| | OPENING THE DOOR. |
| | (2) THE UNLOCKING AND UNLATCHING FROM THE CLASSROOM |
| | SIDE OF THE DOOR |
| | CAN BE ACCOMPLISHED WITHOUT THE USE OF A KEY, TOOL, OR |
| | SPECIAL |
| | KNOWLEDGE OR EFFORT. |
| | (3) THE RELEASING MECHANISM SHALL OPEN THE DOOR LEAF |
| | WITH NOT MORE |
| | THAN ONE RELEASING OPERATION. |
| | (4) THE RELEASING MECHANISM FOR UNLOCKING AND |
| | UNLATCHING SHALL BE |
| | LOCATED AT A HEIGHT NOT LESS THAN 34 IN. (865 MM) AND |
| | NOT EXCEEDING |
| | 48 IN. (1220 MM) ABOVE THE FINISHED FLOOR. |
| | (5) LOCKS, IF REMOTELY ENGAGED, SHALL BE UNLOCKABLE |
| | FROM THE CLASSROOM |
| | SIDE OF THE DOOR WITHOUT THE USE OF A KEY, TOOL, OR |
| | SPECIAL |
| | KNOWLEDGE OR EFFORT. |
| | (6) THE DOOR SHALL BE CAPABLE OF BEING UNLOCKED AND |
| | OPENED FROM |
| | OUTSIDE THE ROOM WITH THE NECESSARY KEY OR OTHER |
| | CREDENTIAL. |
| | (7) THE LOCKING MEANS SHALL NOT MODIFY THE DOOR CLOSER, |
| | PANIC HARDWARE, |
| | OR FIRE EXIT HARDWARE. |
| | (8) MODIFICATIONS TO FIRE DOOR ASSEMBLIES, INCLUDING |
| | DOOR HARDWARE, |
| | SHALL BE IN ACCORDANCE WITH NFPA 80. |
| | (9) THE EMERGENCY ACTION PLAN, REQUIRED BY 14.7.1, |
| | SHALL ADDRESS THE |
| | USE OF THE LOCKING AND UNLOCKING MEANS FROM WITHIN AND |
| | OUTSIDE |
| | THE ROOM. |
| | (10) STAFF SHALL BE DRILLED IN THE ENGAGEMENT AND |
| | RELEASE OF THE LOCKING |
| | MEANS, FROM WITHIN AND OUTSIDE THE ROOM, AS PART OF THE |
| | EMERGENCY |
| | EGRESS DRILLS REQUIRED BY 14.7.2. |
| | |
| | |
| | |
| | 3) SHEET A 1 - THE DOOR SCHEDULE INDICATES NO HARDWARE |
| | INFO FOR THE EXISTING EXTERIOR DOORS 1, 6 & 7. |
| | |
| | 14.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE |
| | PERMITTED. |
| | |
| | 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED |
| | READILY FROM THE |
| | EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. |
| | |
| | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE |
| | OF A KEY, A TOOL, |
| | OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE |
| | EGRESS SIDE. |
| | |
| | 7.2.1.5.10* A LATCH OR OTHER FASTENING DEVICE ON A DOOR |
| | LEAF SHALL BE |
| | PROVIDED WITH A RELEASING DEVICE THAT HAS AN OBVIOUS |
| | METHOD OF OPERATION |
| | AND THAT IS READILY OPERATED UNDER ALL LIGHTING |
| | CONDITIONS. |
| | ADDITIONAL INFO IF APPLICABLE.... |
| | |
| | 7.2.1.5.10.2 THE RELEASING MECHANISM SHALL OPEN THE |
| | DOOR LEAF WITH NOT |
| | MORE THAN ONE RELEASING OPERATION, UNLESS OTHERWISE |
| | SPECIFIED IN |
| | 7.2.1.5.10.3, 7.2.1.5.10.4, 7.2.1.5.10.6, OR |
| | 7.2.1.5.10.7. |
| | |
| | PLEASE PROVIDE THE EXACT TYPE OF HARDWARE FOR EACH |
| | EXTERIOR DOOR. |
| | |
| | |
| | |
| | 4) SHEET CS 1 & LS 1 - THERE IS INDICATION OF A FIRE |
| | SPRINKLER SYSTEM TO BE INSTALLED. |
| | |
| | PER FAC FIRE SPRINKLER DOCUMENTS SHALL BE SUBMITTED BY |
| | AN EOR WITH THIS MASTER PERMIT. |
| | |
| | FAC 61G15-32.002 DEFINES THE FIRE PROTECTION SYSTEM |
| | ENGINEERING DOCUMENT (5) AS WELL AS THE FIRE PROTECTION |
| | SYSTEM LAYOUT DOCUMENT (6). 61G15-32.003 OUTLINES THE |
| | COMMON REQUIREMENTS TO ALL FIRE PROTECTIONS ENGINEERING |
| | DOCUMENTS WITH 32.004 (2) (A-J) OUTLINING THE MINIMUM |
| | INFORMATION TO BE PROVIDED ON FIRE PROTECTION |
| | ENGINEERING DOCUMENTS FOR WATER BASED SYSTEMS. AS |
| | STATED IN THE DEFINITIONS, THE CONTRACTOR IS TO DEVELOP |
| | THE LAYOUT DOCUMENTS BASED ON THE DESIGN CRITERIA |
| | PROVIDED IN THE FIRE PROTECTION ENGINEERING DOCUMENTS |
| | BY THE ENGINEER OF RECORD FOR THE FIRE SPRINKLER |
| | SYSTEM. THE FIRE PROTECTION SYSTEM ENGINEERING |
| | DOCUMENTS ARE SUBMITTED FOR THE MASTER PERMIT (BUILDING |
| | PERMIT PER FBC) AND THE LAYOUT DOCUMENTS ARE SUBMITTED |
| | FOR THE FIRE SPRINKLER INSTALLATION PERMIT. |
| | |
| | PLEASE REVIEW AND PROVIDE SIGNED AND SEALED DOCUMENTS |
| | PER FAC. |
| | |
| | |
| | 4A) THE FIRE SPRINKLER SYSTEM THEN SHALL BE INSTALLED |
| | PER NFPA 101 CH. 14 & NFPA 13 AND SUBMITTED UNDER |
| | SEPARATE PERMIT AND SHOP DRAWINGS. |
| | |
| | PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT |
| | |
| | |
| | |
| | |
| | ANY FIRE LINE UNDEREGROUND WORK SHALL BE INSTALLED |
| | UNDER SEPARATE PERMIT AND SHOP DRAWINGS. |
| | |
| | |
| | |
| | 5) SHEET CS 1 - THERE IS AN INDICATION OF A FIRE ALARM. |
| | |
| | ALL FIRE ALARM WORK SHALL BE INSTALLED PER NFPA 101 CH. |
| | 14 & NFPA 72 AND SUBMITTED UNDER SEPARATE PERMIT AND |
| | SHOP DRAWINGS. |
| | |
| | PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT |
| | |
| | |
| | |
| | |
| | 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |