| Date |
Text |
| 2021-04-30 13:12:40 | DAYCARE |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected]. |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| | 1) PLEASE SHOW THE PREVIOUS USE (OCCUPANCY |
| | CLASSIFICATION) PER FBC CHAPTER 3 |
| | 2) PLEASE SHOW THE TOTAL BUILDING SQUARE FOOTAGE. |
| | 3) PLEASE SHOW ROOM AND CORRIDOR DIMENSIONS FBC 1020.2 |
| | 4) PLEASE SHOW THE FIRE RATING OF THE CORRIDOR WALLS TO |
| | COMPLY WITH FBC 466.8 |
| | 5) FIRE RATED PARTITIONS - 708.4 CONTINUITY. |
| | FIRE PARTITIONS SHALL EXTEND FROM THE TOP OF THE |
| | FOUNDATION OR FLOOR/CEILING ASSEMBLY BELOW TO THE |
| | UNDERSIDE OF THE FLOOR OR ROOF SHEATHING, SLAB OR DECK |
| | ABOVE OR TO THE FIRE-RESISTANCE-RATED FLOOR/CEILING OR |
| | ROOF/CEILING ASSEMBLY ABOVE, AND SHALL BE SECURELY |
| | ATTACHED THERETO. |
| | 6) SMOKE BARRIERS - 709.4 CONTINUITY. |
| | SMOKE BARRIERS SHALL FORM AN EFFECTIVE MEMBRANE |
| | CONTINUOUS FROM THE TOP OF THE FOUNDATION OR |
| | FLOOR/CEILING ASSEMBLY BELOW TO THE UNDERSIDE OF THE |
| | FLOOR OR ROOF SHEATHING, DECK OR SLAB ABOVE, INCLUDING |
| | CONTINUITY THROUGH CONCEALED SPACES, SUCH AS THOSE |
| | FOUND ABOVE SUSPENDED CEILINGS, AND INTERSTITIAL |
| | STRUCTURAL AND MECHANICAL SPACES. |
| | 7) DOORS AND GLAZING IN FIRE PARTITIONS NEED TO HAVE |
| | FIRE RATINGS THAT COMPLY WITH FBC 716.5 |
| | 8) BUILDING CONSTRUCTION TYPE SHOULD BE VB NOT IV AS |
| | SHOWN ON THE DRAWINGS IN SEVERAL PLACES - SEE FBC |
| | CHAPTER 6 |
| | 9) RESTROOMS 109 AND 112 FBC ACCESSIBILITY 604.9 FOR |
| | AGE GROUP 3 TO 4 THE SPECIFICATIONS OF ONE AGE GROUP |
| | SHOULD BE APPLIED CONSISTENTLY IN THE INSTALLATION OF A |
| | WATER CLOSET AND RELATED ELEMENTS. CENTER LINE FOR |
| | WATER CLOSET SHOULD BE 12" - THE GRAB BAR MAXIMUM |
| | HEIGHT SHOULD BE 20" TO THE TOP GRIPING SURFACE NOT THE |
| | CENTERLINE AS SHOWN. |
| | 10) PLEASE SHOW ADA RESTROOM MIRROR MAXIMUM HEIGHT TO |
| | THE BOTTOM OF THE REFLECTION FBC 603.3 MIRRORS. |
| | MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL |
| | BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| | SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND. |
| | 11) ADA RESTROOM PAPER TOWEL DISPENSER - THE OUTLET OF |
| | THE DISPENSER SHOULD BE SHOWN TO MEET THE REACH RANGES |
| | SEE FBC ACCESSIBILITY 308.1 (SEE ALSO THE ADVISORY FOR |
| | AGE GROUPS) |
| | 12) PRODUCT APPROVAL (FL14237-R3) FOR THE EXTERIOR DOOR |
| | HAS EXPIRED - PLEASE PROVIDE THE UPDATED VERSION |
| | (FL14237-R5) FRONT PAGES AND THE INSTALLATION |
| | INSTRUCTIONS. DOOR PRODUCT APPROVAL NEEDS TO BE |
| | REVIEWED AND MARKED APPROVED BY THE DESIGNER OF RECORD |
| | OR BE LISTED BY PRODUCT APPROVAL NUMBER ON THE |
| | DRAWINGS. |
| | |