Plan Review Notes
Plan Review Notes For Permit 21031438
Permit Number 21031438
Review Stop B
Sequence Number 1
Notes
Date Text
2021-04-21 14:07:14RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21031438
  
 1-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. 1106
 FBC-EXISTING BUILDING AND SEC. R101.5 FBC-ENERGY
 CONSERVATION.
 NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL
 REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID
 CONFLICTS/DELAYS.
  
 2-LOT DRAINAGE
 PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH SEC.
 1101.1 FBC-EXISTING BUILDING AND THE FOLLOWING:
 R401.3 FBC-RESIDENTIAL.
 SEC. 107.2.5 CITY AMENDMENTS.
 SEC. 110.9 CITY AMENDMENTS.
  
 3- BEDROOM WINDOWS: SPECIFY SIZE AND TYPE OF EXISTING
 WINDOW AND SIZE AND TYPE OF PROPOSED WINDOWS TO VERIFY
 COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC. 702.5
 FBC-EXISTING BUILDING.
 NOTE: CLARIFY WHY FLOOR PLAN SHOWS WHAT LOOKS LIKE
 CASEMENT WINDOWS, WHILE EXTERIOR ELEVATIONS SHOW WHAT
 LOOKS LIKE SINGLE HUNG WINDOWS.
  
 4- THERE IS AN EXISTING SWIMMING POOL IN THIS PROPERTY.
 PROVIDE SPECIFICATIONS SHOWING HOW THE PROPOSED
 ADDITION WILL COMPLY WITH THE RESIDENTIAL SWIMMING
 BARRIER REQUIREMENT REQUIRED BY SEC. R4501.17
 FBC-RESIDENTIAL. SEC. 1101.1 FBC-EXISTING BUILDING
  
 5- DESIGN PRESSURES SHOWN ON SHEET A-2 AND S-2 DON'T
 MATCH. ALSO, CLARIFY WHY USING 20 S.F. AS THE TRIBUTARY
 AREA. PROVIDE DESIGN PRESSURES FOR EACH EFFECTIVE
 TRIBUTARY AREA OR IF USING THE WORST CASE SCENARIO TO
 COVER ALL COMPONENTS AND CLADDING DESIGN PRESSURES,
 THEN NEED TO USE THE ONE WITH THE LOWEST EFFECTIVE
 AREA. SEE FOOTNOTES ON TABLE R301.2(2) FBC-RESIDENTIAL
 AND REVISE AS REQUIRED.
 SEC. 1101.1 FBC-EXISTING BUILDING.
  
  
 6- SPECIFY ATTIC ACCESS SIZE AND LOCATION FOR THE NEW
 ADDITION. SEC. 1101.1 FBC-EXISTING BUILDING. SEC.
 R307.1 FBC-RESIDENTIAL.
  
 7-PROVIDE PRODUCT APPROVAL AS REQUIRED BY SEC. 1101.1
 FBC-EXISTING BUILDING. FAC 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
  
 A)ROOF SHINGLES.
 B)EXTERIOR SWING DOORS AS SHOWN ON PLANS.
 C)SLIDING GLASS AS SHOWN ON PLANS.
 D)WINDOWS AS SPECIFIED ON PLANS (COORDINATE WITH ITEM
 #3 ABOVE).
  
 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 9-PROVIDE STRUCTURAL BUCK DETAILS FOR WINDOWS AND DOORS
 (SWING AND SLIDING GLASS DOORS). SPECIFY THE SIZE OF
 THE STRUCTURAL BUCK. STRUCTURAL BUCK NEEDS TO PROVIDE
 FULL SUPPORT TO THE DOOR FRAME AS REQUIRED BY SEC.
 R609.7.2.1 FBC-RESIDENTIAL.
 SEC. 1101.1 FBC-EXISTING BUILDING.
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  