| 2021-04-09 12:45:42 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21031429 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) A MECHANICAL SUB-PERMIT IS REQUIRED. |
| | |
| | 2) FS 471.003 (H): THE MECHANICAL EQUIPMENT SIZING |
| | CALCULATIONS ALONG WITH THE MECHANICAL SYSTEM DESIGN |
| | MUST BE DESIGNED BY A FLORIDA LICENSED ENGINEER OR THE |
| | MECHANICAL CONTRACTOR THAT HOLDS THE PERMIT FOR THE |
| | SPECIFIC PROJECT WHICH HE OR SHE INSTALLS. |
| | PLEASE, HAVE EITHER A LICENSED ENGINEER, PROVIDE A |
| | SIGNED AND SEALED MECHANICAL EQUIPMENT SIZING |
| | CALCULATION AND A SIGNED AND SEALED MECHANICAL DRAWING, |
| | OR |
| | THE MECHANICAL CONTRACTOR INSTALLING THE SYSTEM SHALL |
| | PROVIDE THE EQUIPMENT SIZING CALCULATIONS AND A CODE |
| | COMPLIANT DESIGN. CONTRACTOR SHALL INCLUDE HIS OR HER |
| | PRINTED NAME AND SIGNATURE PER 2017 WPB AMENDMENTS TO |
| | THE FLORIDA BUILDING CODE, CHAPTER 1, SECTION 107.2.1. |
| | FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS |
| | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE |
| | OF THE PERSON RESPONSIBLE FOR THE DESIGN. |
| | |
| | |
| | THERE IS NO MECHANICAL SUB PERMIT FOR THIS JOB. |
| | |
| | A REVIEW OF THE DRAWINGS WILL BE COMPLETED ONCE THE |
| | LICENSED ENGINEER HAS SUBMITTED THE REQUIRED DOCUMENTS. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |