| 2021-04-08 22:25:59 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. SERVICE ENTRANCE CONDUCTORS ARE OF INSUFFICENT SIZE. |
| | LOAD FOR SERVICE IS SHOWN AS 271AMPS, AT 83% SERVICE |
| | ENTRANCE CONDUCTORS MUST CARRY A LOAD OF 225AMPS. 4/0 |
| | CU REQUIRED. NEC 110.3B NEC 230.23 |
| | |
| | 2. EQUIPMENT GROUND SHOWN FROM METER-CAN TO MDP, |
| | EQUIPMENT GROUND ORIGINATES AT FIRST MEANS OF |
| | DISCONNECT, WHICH WOULD BE THE MDP, REMOVE EQUIPMENT |
| | GROUND FROM CONDUIT. |
| | |
| | 3. NO MAINS SHOWN IN MDP, WHAT ARE THE SIZE OF THE |
| | MAINS?? FBC 107.2.1 |
| | |
| | 4. SEVERAL DISCREPANCIES ARE SHOWN ON RISER DIAGRAM, |
| | ONE NOTE SAYS " PARALLEL 3-350MCM RUNS" ANOTHER SAYS |
| | "PARALLEL 3-3/0 RUNS". PROVIDE ACCURATE AND CODE |
| | COMPLIANT RISER DIAGRAM. FBC 107.2.1 |
| | |
| | 5. SMOKE/CARBON ALARMS REQUIRED OUTSIDE OF BEDROOMS |
| | WITHIN 10' PER FBC-R 314 AND 315, PROVIDE CORRECTIONS. |
| | |
| | 6. SMOKE ALARMS AND SMOKE/CARBON ALARMS MUST BE WITHIN |
| | 12'' OF HIGHEST POINT OF CEILINGS. A NOTE ON PLAN |
| | STATING THIS WILL SUFFICE. FBC 107.2.1 NFPA 72 |
| | |
| | 7. GENERATOR ON PLANS REQUIRES A SEPARATE PERMIT WITH |
| | SEPARATE DRAWINGS. ATS CAN STAY ON PLAN BUT REMOVE |
| | GENERATOR FROM PLAN. FBC 107.2.1 FBC 105.1 |
| | |
| | 8. NO SPECS SUBMITTED OR SIZE OF ATS IS SHOWN ON PLAN. |
| | PROVIDE CORRECTIONS. FBC 107.2.1 |
| | |
| | 9. GARAGE DOOR OPENER RECEPTACLES REQUIRED GFCI |
| | PROTECTION PER NEC 210.8. PROVIDE CORRECTIONS. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| | UILDING-PERMIT-FORMS |
| | |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | [email protected] |
| | CELL: 561-657-1653 |
| | |