| 2021-05-12 14:06:00 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21031410 |
| | 5/12/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS LS100. AD200, A200 & A300: IF THERE IS NO |
| | EXEMPTION BEING CITED FOR REVIEW, THEN THE PROPOSED |
| | BATHROOMS SHALL BE DESIGNED AND CONSTRUCTED IN |
| | ACCORDANCE WITH THE FBC- 2020 7TH EDITION ACCESSIBILITY |
| | CODE. PLEASE REVISE THE APPLICABLE CODE DATA ON LS100. |
| | |
| | 2) A200 & A300: THE PLANS ARE INDICATING NON- |
| | COMPLIANCE FOR REQUIRED CLEAR FLOOR SPACES AT THE NEW |
| | WATER CLOSETS AND LAVATORIES; AND INSUFFICIENT |
| | INFORMATION AND DETAILS AS REQUIRED BY THE FBC ACC. |
| | PLEASE REVIEW THE LIST OF REQUIRED DETAILS BELOW AND |
| | REVISE THE PLANS TO SHOW COMPLIANCE: |
| | A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE |
| | WATER CLOSETS- SECTION 604.3. |
| | B) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE |
| | LAVATORIES- SECTION 606.2. |
| | C) TURNING SPACE DIAMETERS- SECTION 304.3. |
| | D) CENTERLINES OF THE WATER CLOSET FROM THE SIDE WALLS- |
| | SECTION 604.2. |
| | E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED |
| | FLOORS- SECTION 604.4. |
| | F) HEIGHTS OF THE LAVATORY SINKS RIMS FROM THE FINISHED |
| | FLOORS- SECTION 606.3. |
| | G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO |
| | THE REFLECTIVE SURFACES- SECTION 603.3 |
| | H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4, |
| | FIGURES 604. |
| | I) LOCATION OF THE WATER CLOSET FLUSH CONTROLS - |
| | SECTION 604.6. |
| | J) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED |
| | FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND |
| | FIGURE 604.7. |
| | K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION |
| | 606.2 |
| | SHOWERS: |
| | L) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | SHOWER- SECTION 608.2.2. |
| | M) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE ACCESSIBLE SHOWER- SECTION 608.3.2. |
| | N) LOCATION OF CONTROL, FAUCET, AND SHOWER SPRAY IN THE |
| | SHOWER- SECTION 608.5.2. |
| | O) SHOWER SPRAY UNIT SPECIFICATIONS PER SECTION 608.6. |
| | P) LOCATION OF ACCESSIBLE SHOWER SEAT AND DIMENSIONS- |
| | SECTIONS 610.3 & 610.3.2 (FIGURE 610.3.2). |
| | |
| | 4) A400: THE FINISH SCHEDULE SPECIFICATIONS INDICATE |
| | GWB FOR THE RESTROOM AND SHOWER WALLS. GWB IS |
| | NON-COMPLIANT MATERIAL FOR BOTH THE ROOM WALLS AND |
| | SHOWER WALLS- SEE SECTION 310.3 FBC P, AND SECTIONS |
| | 1210.2.2 & 12102.3 FBC B. |
| | |
| | 5) PD101: SHOW AREAS OF SLAB DEMOLITION AND PROVIDE |
| | SLAB REPAIR DETAILS- SECTION 107.2.1 WPB. |
| | |
| | 6) P01, PD1.1, & P1.1: WHAT DO THE WATER LINE SYMBOL |
| | ABBREVIATIONS A.C AND B.F INDICATE? THEY ARE NOT |
| | DEFINED ON ANY OF THE PLANS THAT I SEE- SECTION 107.2.1 |
| | WPB. |
| | |
| | 7) P02: PLACE A NOTE ON THE PLAN THAT THE RPZ WILL BE |
| | INSTALLED UNDER A SEPARATE PERMIT AS REQUIRED BY THE |
| | CITY OF WEST PALM BEACH BUILDING DEPT- SECTION 105.1 & |
| | 107.2.1 WPB. |
| | |
| | 8) P02: THERE IS NOTE REFERENCING A CIVIL UTILITY SITE |
| | PLAN WHICH HAS NOT BEEN SUBMITTED. PLEASE PROVIDE THE |
| | PLAN FOR CLARIFICATION- SECTION 107.2.1 WPB. |
| | |
| | 9) P10: PROVIDE A CLEANOUT AT THE JUNCTION OF THE |
| | WOMEN'S BUILDING DRAIN/SEWER JUNCTION- SECTION 708.1.3 |
| | FBC P. |
| | |
| | 10) P1.1 & P7.0: INDICATE HOW THE WATER SOFTENER WILL |
| | BE PROTECTED AGAINST CONTAMINATION- SECTION 608.13 FBC |
| | P. |
| | |
| | 11) PROVIDE A SHOWER PAN DETAIL- SECTION 421.5.2 FBC P. |
| | |
| | 12) P6.0: PROVIDE THE EFFICIENCY RATING OF THE NEW |
| | WATER HEATER AND SUBMIT MANUFACTURER'S SPECIFICATIONS- |
| | TABLE C404.2 FBC EC. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |