| 2021-06-22 12:21:54 | CONDO REMODEL |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected]. |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| | 1) PRODUCT APPROVAL FOR THE SWING DOOR NEEDS TO BE |
| | REVIEWED AND MARKED APPROVED BY THE DESIGNER OF RECORD. |
| | FBC WPB 107.3.4 |
| | 2) PLEASE PROVIDE A WINDOW AND DOOR SCHEDULE SHOWING |
| | THE SIZES AND TYPES OF EXTERIOR WINDOWS AND DOORS. |
| | 3) FLOORING TEST REPORTS PROVIDED SHOW A DROP CEILING |
| | AS PART OF THE ASSEMBLY TESTED. (EXISTING BUILDING MAY |
| | NOT HAVE A DROP CEILING SIMULAR TO THE TEST REPORT). |
| | 4) FLOORING TEST REPORTS PROVIDED ARE FOR AN 8" |
| | CONCRETE SLAB - PLEASE HAVE THE DESIGNER STATE ON THE |
| | DRAWINGS THE THICKNESS OF THE EXISTING CONCRETE SLAB OR |
| | THE DESIGNER CAN REVIEW AND MARK THE TEST REPORTS |
| | APPROVED FBC WPB 107.3.4 |
| | |
| | THE FOLLOWING ACUSTICAL TEST REPORTS ARE REQUIRED: FOR |
| | THE NEW TILE FLOOORING |
| | |
| | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO |
| | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST |
| | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE |
| | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) |
| | |
| | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| | THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM |
| | CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED |
| | GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS |
| | ATTACHED TO THE FLOORING) |
| | |
| | |
| | |