| Plan Review Notes For Permit 21031323 |
| Permit Number |
21031323 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-04-13 15:10:44 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) RESOLVED. | | | | | | 2) NOT RESOLVED. [THE SIGNED AND SEALED WIND LOAD CHART | | | THAT WAS SUBMITTED IS FOR EXPOSURE CATEGORY C AND THIS | | | BUILDING IS LOCATED IN EXPOSURE CATEGORY D. SUBMIT A | | | WIND LOAD CHART FOR BUILDINGS TALLER THAN 60 FEET IN | | | EXPOSURE CATEGORY D. SPECIFY THE BUILDING HEIGHT AND | | | THE WALL ZONE FOR EACH OF THE WINDOWS.] THE WINDOWS ARE | | | LOCATED IN A HIGH RISE BUILDING THAT IS MORE THAN 60 | | | FEET IN HEIGHT WITH A 170 MPH WIND SPEED IN EXPOSURE | | | CATEGORY D. SUBMIT SIGNED AND SEALED COMPONENT AND | | | CLADDING WIND LOAD PRESSURES FROM A FLORIDA LICENSED | | | ENGINEER FOR EACH OF THE WINDOW OPENINGS. FBC 1609 | | | | | | |
|