| Plan Review Notes For Permit 21031323 |
| Permit Number |
21031323 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-04-09 08:44:09 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) REVISE NOTE (4) ON SHEET A1 TO SPECIFY THE 2020 FBC | | | SEVENTH EDITION. THE PLAN REFERENCES THE FBC SIXTH | | | EDITION (2017). THE FBC SEVENTH EDITION (2020) WENT | | | INTO EFFECT ON DECEMBER 31, 2020. ALL NEW PERMITS | | | APPLIED FOR ON OR AFTER THAT DATE ARE REQUIRED TO | | | COMPLY WITH AND REFERENCE THE 2020 FBC SEVENTH EDITION. | | | FS CHAPTER 553 | | | | | | 2) THE WINDOWS ARE LOCATED IN A HIGH RISE BUILDING THAT | | | IS MORE THAN 60 FEET IN HEIGHT WITH A 170 MPH WIND | | | SPEED IN EXPOSURE CATEGORY D. SUBMIT SIGNED AND SEALED | | | COMPONENT AND CLADDING WIND LOAD PRESSURES FROM A | | | FLORIDA LICENSED ENGINEER FOR EACH OF THE WINDOW | | | OPENINGS. FBC 1609 | | | | | | |
|