2021-04-07 13:15:4604/07/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR
 THE MAXIMUM SYSTEM FLOW. THE TDH CALCULATIONS MUST
 INCLUDE ALL THE SYSTEM COMPONENTS, INCLUDING SUCTION
 AND RETURN PIPING, FITTINGS, VALVES, FILTER, AND
 CHLORINATOR. ALL SYSTEM COMPONENTS EXCEPT THE PUMP.
  
 2. PLEASE SUBMIT THE POOL PUMP CURVE. IDENTIFY ON THE
 PUMP CURVE WHICH CURVE KEY IS SPECIFIC TO THE PUMP
 BEING INSTALLED ON THIS POOL. THIS IS NEEDED TO CONFIRM
 THE MAXIMUM SYSTEM FLOW FROM THE TDH CALCULATIONS PER
 THE ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, 4.4.9.1.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  