| 2021-04-07 17:54:15 | 04/07/21 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. PLEASE SUBMIT MANUFACTURER?S SPECIFICATION |
| | SHEETS/INSTALLATION MANUAL FOR POOL HEATER GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH 2020 FBC RES. SEC. |
| | G2408.1. |
| | |
| | 2. THE CITY HAS A RECORD OF AN EXISTING GAS METER |
| | CONNECTED TO AN EXISTING POOL HEATER. IS THIS METER |
| | REPLACING THE OLD SYSTEM, AND IS SO THE BTU LOAD OF THE |
| | EXISTING GAS SYSTEM MUST BE ADDED INTO THE TOTAL BTU |
| | LOAD ON THE SYSTEM TO ENSURE THE EXISTING SYSTEM IS |
| | SIZED CORRECTLY. IF UNDERSIZED, THE EXISTING SYSTEM |
| | MUST BE REDONE TO ENSURE A SAFE OPERATING SYSTEM. |
| | SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS THE TYPE |
| | OF EXISTING APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, |
| | THE PIPE SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND |
| | THE DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE |
| | POINT OF DELIVERY TO THE MOST REMOTE OUTLET AND THE |
| | LOAD OF THE SECTION. NOTE: IF THE EXISTING SYSTEM IS |
| | LESS THAN A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS |
| | INCREASED TO 2 PSI, A LINE PRESSURE REGULATOR IS |
| | REQUIRED AT ALL THE EXISTING APPLIANCES PER THE 2020 |
| | FBC RES. SECS. G2412.4, G2412.8, G2413.1, G2413.2, |
| | G2413.3. |
| | |
| | NOTE IF THIS IS A NEW METER, CLARIFY AND PUT ON PLANS A |
| | SECOND NEW METER. |
| | |
| | 3. A REGULATOR MAY BE REQUIRED TO BRING THE SYSTEM DOWN |
| | TO 10.5 WC. PLEASE SUBMIT THE MANUFACTURER?S |
| | SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS |
| | INSTALLED ON THE BUILDING'S EXTERIOR SHALL BE APPROVED |
| | FOR OUTDOOR INSTALLATION PER THE 2020 FBC RES. SEC. |
| | G2421.1. |
| | |
| | 4. PLEASE LABEL AND SHOW ALL SHUT-OFF, DRIP LEG, AND |
| | UNIONS IN FRONT OF REGULATOR 1? OF EITHER SIDE PER THE |
| | 2020 FBC RES. SEC G2421.2. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |