| 2021-04-22 16:38:40 | 1ST REVIEW FBC-2020 RES. FUEL GAS |
| | PERMIT- 21031243 |
| | 4/22/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE GAS PLANS INCLUDING A GAS PIPING RISER, |
| | COMBUSTION AIR CALCULATIONS AND VENTING PLANS- SECTIONS |
| | 107.2.1, 107.3.5.3 WPB AND FBC RES. FUEL GAS. |
| | |
| | 2) GAS RISER SHALL INCLUDE: |
| | A) TYPE OF GAS- NATURAL OR LP. |
| | B) LOCATION OF METER OR LP TANK(S) AND1ST STAGE |
| | DELIVERY PRESSURE. |
| | C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. |
| | D) TYPES AND SIZES OF PIPING. |
| | E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER |
| | TO THE MOST REMOTE APPLIANCE OUTLET. |
| | F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. |
| | G) LOCATIONS OF 2ND STAGE REGULATORS, SHUTOFF VALVES, |
| | AND PIPE UNIONS. |
| | H) INLET AND OUTLET PRESSURES AT REGULATORS. |
| | I) LOCATIONS AND TYPES OF PIPE SLEEVES. |
| | K) PIPE SIZING TABLES OR PIPE SIZING METHOD USED. |
| | |
| | 3) PROVIDE COMBUSTION AIR CALCULATIONS AND INDICATE HOW |
| | THE AIR WILL BE PROVIDED TO THE GAS RANGE- SECTION- |
| | G2407.1 FBC RES. |
| | |
| | 4) PROVIDE MAKEUP AIR FOR THE DRYER AND INDICATE HOW |
| | THE MAKEUP AIR WILL BE PROVIDED- G2439.5 FBC RES. |
| | |
| | 5) PROVIDE EQUIPMENT SCHEDULES FOR THE TANKLESS WATER |
| | HEATERS INDICATING MAKES AND MODELS, BTU CAPACITIES, |
| | AND EFFICIENCY RATING PER TABLE C404.1 FBC EC. |
| | |
| | 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL GAS |
| | FIRED APPLIANCES- SECTION G2408.1 FBC RES. |
| | |
| | 7) SUBMIT A GAS SUB-PERMIT IF THE INSTALLATIONS ARE TO |
| | BE INCLUDED UNDER THE MASTER PERMIT- SECTION 105.1 WPB. |
| | IF THE GAS INSTALLATIONS ARE TO BE UNDER A SEPARATE |
| | PRIMARY PERMIT, PLEASE PLACE A NOTE ON THE PLAN. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |