| 2021-04-22 15:05:05 | CODES IN EFFECT |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020 |
| | 7TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | REVIEW STATUS: FAILED. PLEASE SEE COMMENTS BELOW: |
| | |
| | 1) SHEET E101 ELECTRICAL PLAN: ELECTRICAL NOTE NO. 6. |
| | REFERENCES TO CODES ARE OUTDATED. PLEASE SEE BELOW FOR |
| | CURRENT CODES AND UPDATE NOTE TO REFLECT THEM. |
| | |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020 |
| | 7TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | |
| | 2) SHEET E101 ELECTRICAL PLAN: ELECTRICAL NOTE NO. 28. |
| | CURRENT FLORIDA ENERGY CODE 2020 7TH EDITION REQUIRES |
| | THAT: |
| | |
| | "R 404.1 NOT LESS THAN 90 PERCENT OF THE LAMPS IN |
| | PERMANENTLY INSTALLED LUMINAIRES SHALL HAVE AN EFFICACY |
| | OF AT LEAST 45 LUMENS-PER-WATT OR SHALL UTILIZE LAMPS |
| | WITH AN EFFICACY OF NOT LESS THAN 65 LUMENS-PER-WATT." |
| | |
| | PLEASE UPDATE NOTE TO REFLECT NEW CODE REQUIREMENTS |
| | |
| | 3) PLEASE PROVIDE UPDATED PANEL SCHEDULE FOR EXISTING |
| | PANEL AND NEW PANEL. INCLUDE AIC RATINGS, MCB SIZES. |
| | |
| | 4) SHEET A400 (SCHEDULES - RISERS): LOAD CALCULATION |
| | FOR NEW PANEL INDICATES A TOTAL DEMAND LOAD OF 72.8 |
| | AMPS |
| | BUT RISER DIAGRAM SPECIFIES A #6 CU FEEDER FROM |
| | EXISTING PANEL WHICH ONLY HAS AN AMPACITY OF 65 AMPS. |
| | PLEASE PROVIDE CORRECTION. THE CALCULATIONS ARE LABELED |
| | "NEW SERVICE LOAD CALCULATION" BUT THIS IS NOT A NEW |
| | SERVICE BUT LOAD CALCUTIONS FOR GUEST HOUSE PANEL. |
| | PLEASE LABEL PROPERLY. |
| | |
| | 5) NEW PANEL FOR GUEST HOUSE MUST BE GROUNDED AS PER |
| | NEC 250.32. PLEASE INCLUDE GROUNDING DETAILS FOR GUEST |
| | PANEL ON RISER DIAGRAM. |
| | |
| | |
| | ENRIQUE QUINONEZ P.E. |
| | ELECTRICAL PLANS EXAMINER |
| | DEVELOPMENT SERVICES |
| | CITY OF WEST PAM BEACH |
| | 401 CLEMATIS STREET, 1ST FLOOR |
| | WEST PALM BEACH, FL 33401 |
| | |
| | FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS, |
| | 561-805-6746. |
| | |