| 2021-04-07 11:31:01 | 04/07/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | 1. PLEASE SUBMIT DOCUMENTATION THAT THE PROPOSED DEVICE |
| | IS LEAD-FREE, WHICH CONTAINS NOT MORE THAN 0.25-PERCENT |
| | LEAD. |
| | |
| | 2. PIPE, PIPE FITTINGS, JOINTS, VALVES, FAUCETS, AND |
| | FIXTURE FITTINGS UTILIZED TO SUPPLY WATER FOR DRINKING |
| | OR COOKING PURPOSES SHALL COMPLY WITH NSF 372 AND SHALL |
| | HAVE A WEIGHTED AVERAGE LEAD CONTENT 0.25 PERCENT OR |
| | LESS PER THE 2020 FBC SEC. P 605.2.1 LEAD CONTENT OF |
| | DRINKING WATER PIPE AND FITTINGS. |
| | |
| | 3. THE DOCUMENT SUBMITTED IS NOT THE CORRECT ONE. YOUR |
| | OFFICE HAS BEEN CONTACTED BEFORE ON THE SAME MATTER, SO |
| | PLEASE MAKE A NOT-AS-IT BEASUSE THAT WILL PREVENT DELAY |
| | IN FUTURE BACKFLOW REVIEWS. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |