| Plan Review Notes For Permit 21031237 |
| Permit Number |
21031237 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-04-08 13:05:47 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) FLOOR PLAN SHEET - THERE IS NO ADDRESS INDICATED ON | | | THE FLOOR PLAN. | | | | | | PLEASE PROVIDE. | | | | | | | | | 2) FLOOR PLAN SHEET - THERE APPEARS TO BE INDICATORS | | | WITHIN THE LAUNDRY ROOM; HOWEVER, THERE IS NOTHING | | | INDICATED WITHIN THE SCOPE OF WORK. | | | | | | PLEASE PROVIDE CLARIFICATIONS. | | | | | | 2A) FLOOR PLAN SHEET - ARE ALL WALLS EXISTING? ARE ANY | | | WALLS RELOCATED? | | | | | | PLEASE PROVIDE CLARIFICATIONS. | | | | | | | | | 3) FLOOR PLAN SHEET - THERE IS CEILING WORK INDICATED. | | | | | | ALL FIRE SPRINKLERS SHALL BE PROTECTED FROM | | | DAMAGE/PAINT AND REMAIN FUNCTIONAL THROUGHOUT DEMO AND | | | CONSTRUCTION. | | | | | | ANY FIRE SPRINKLER, EVEN SPRINKLER HEAD REPLACEMENT, | | | SHALL BE DONE UNDER SEPARATE PERMIT AND SHOP DRAWING. | | | | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|