Plan Review Notes
Plan Review Notes For Permit 21031237
Permit Number 21031237
Review Stop B
Sequence Number 1
Notes
Date Text
2021-04-08 13:59:21REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) IS THE UNIT ON THE FIRST FLOOR? IS THERE A UNIT
 BELOW THIS UNIT? - IF NO UNIT BELOW THIS ONE WRITE ON
 THE DRAWINGS THAT THERE IS NO UNIT BELOW THIS UNIT.
 FBC 1207.2AIRBORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS AND SLEEPING UNITS FROM EACH
 OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A
 SOUND TRANSMISSION CLASS OF NOT LESS THAN 50, OR NOT
 LESS THAN 45 IF FIELD TESTED, FOR AIRBORNE NOISE WHEN
 TESTED IN ACCORDANCE WITH ASTM E90.
 FBC 1207.3STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS AND
 SLEEPING UNITS OR BETWEEN A DWELLING UNIT OR SLEEPING
 UNIT AND A PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE
 SHALL HAVE AN IMPACT INSULATION CLASS RATING OF NOT
 LESS THAN 50, OR NOT LESS THAN 45 IF FIELD TESTED, WHEN
 TESTED IN ACCORDANCE WITH ASTM E492.