| Plan Review Notes For Permit 21031237 |
| Permit Number |
21031237 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-04-08 13:59:21 | REMODEL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) IS THE UNIT ON THE FIRST FLOOR? IS THERE A UNIT | | | BELOW THIS UNIT? - IF NO UNIT BELOW THIS ONE WRITE ON | | | THE DRAWINGS THAT THERE IS NO UNIT BELOW THIS UNIT. | | | FBC 1207.2AIRBORNE SOUND. | | | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES | | | SEPARATING DWELLING UNITS AND SLEEPING UNITS FROM EACH | | | OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A | | | SOUND TRANSMISSION CLASS OF NOT LESS THAN 50, OR NOT | | | LESS THAN 45 IF FIELD TESTED, FOR AIRBORNE NOISE WHEN | | | TESTED IN ACCORDANCE WITH ASTM E90. | | | FBC 1207.3STRUCTURE-BORNE SOUND. | | | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS AND | | | SLEEPING UNITS OR BETWEEN A DWELLING UNIT OR SLEEPING | | | UNIT AND A PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE | | | SHALL HAVE AN IMPACT INSULATION CLASS RATING OF NOT | | | LESS THAN 50, OR NOT LESS THAN 45 IF FIELD TESTED, WHEN | | | TESTED IN ACCORDANCE WITH ASTM E492. |
|