| Plan Review Notes For Permit 21031236 |
| Permit Number |
21031236 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2022-07-11 11:43:17 | 2ND PLUMBING REVIEW | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. NOT CHANGED - 2020 FPC 607.2 - THE DETAIL FOR HOT | | | WATER SUPPLY STATES "100 FEET TO THE FARTHEST FIXTURE" | | | AND IT IS 50 FEET MAXIMUM OR A CIRCULATING LINE IS | | | REQUIRED. PLEASE DETAIL THE DISTANCE AND SUPPLY A | | | RECIRCULATING LINE IF REQUIRED. | | | | | | 2. DONE | | | | | | 3. DONE | | | | | | 4. DONE | | | | | | 5. DONE | | | | | | 6. DONE | | | | | | 7. CHANGED CREATING A NEW COMMENT - SEE COMMENT 8 | | | | | | 8. 2020 FPC 901.2.1 - THE WATER CLOSET IS NOT VENTED. | | | IT CONNECTS TO A BUILDING DRAIN WITHOUT A VENT BETWEEN | | | THE FIXTURE TRAP AND THE FIXTURE DRAIN'S CONNECTION TO | | | A HORIZONTAL BRANCH OR DRAIN. | | | | | | | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | |
|