| 2022-06-03 06:23:01 | 1ST PLUMBING REVIEW |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. 2020 FPC 607.2 - THE DETAIL FOR HOT WATER SUPPLY |
| | STATES "100 FEET TO THE FARTHEST FIXTURE" AND IT IS 50 |
| | FEET MAXIMUM OR A CIRCULATING LINE IS REQUIRED. PLEASE |
| | DETAIL THE DISTANCE AND SUPPLY A RECIRCULATING LINE IF |
| | REQUIRED. |
| | |
| | 2. 2020 FEC C404.4 - THE MINIMUM PIPE INSULATION SHAL |
| | BE IN COMPLIANCE WITH TABLE C403.2.10, YOU HAVE LISTED |
| | TABLE 607.2.1 OF THE FPC. PLEASE CORRECT. |
| | |
| | 3. 2017 WPB AMENDS 107.2.1 - YOUR SANITARY ISO HAS |
| | INCORRECTLY LABELED THE LAVATORY NEAR THE 3 COMP SINK |
| | (SHOULD BE HAND SINK) AND THE HAND SINK NEAR THE WC |
| | (SHOULD BE LAV). |
| | |
| | 4. 2020 FPC - 607.1.1 - YOU HAVE LISTED A MIXING DEVICE |
| | FOR THE TEMPERED WATER AT THE PUBLIC LAV, BUT HAVE NOT |
| | LISTED A MXING DEVICE FOR "HOT WATER DELIVERY". PER |
| | 607.1.1, THE THERMOSTAT ON THE WATER HEATER SHALL NOT |
| | BE THE LIMITING DEVICE FOR PROVIDING HOT WATER. PLEASE |
| | SHOW A DEVICE OTHER THAN THE THERMOSTAT ON THE WATER |
| | HEATER THAT LIMITS THE TEMPERATURE OF "HOT WATER". THIS |
| | IS IN ADDITION TO THE MIXING DEVICE FOR TEMPERED WATER |
| | AT THE LAV. |
| | |
| | 5. 2020 FPC 708.1.3 - PLEASE DETAIL THE REQUIRED |
| | CLEANOUT AT THE JUNCTION OF THE BUILDING DRAIN AND THE |
| | SEWER. IF IT IS A WALKWAY OR TRAFFIC AREA, PLEASE SHOW |
| | THE DETAILS COMPLYING WITH 2020 FPC 708.1.10.2. |
| | |
| | 6. 2020 FPC 708.1.1 - YOU DO NOT HAVE THE REQUIRED |
| | CLEANOUT ON THE HORIZONTAL BUILDING DRAIN WITHIN THE |
| | BUILDING. |
| | |
| | 7. 2020 FPC 905.4 - THE VENT AT THE MOP SINK AND THE |
| | VENT AT THE WATER CLOSET ARE NOT ALLOWED TO BE |
| | HORIZONTAL UNTIL THEY ARE 6" ABOVE THE FIXTURE(S) |
| | SERVED. PLEASE RECONFIGURE AND SHOW A COMPLIANT VENTING |
| | SYSTEM. |
| | |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |