Plan Review Notes
Plan Review Notes For Permit 21031236
Permit Number 21031236
Review Stop P
Sequence Number 2
Notes
Date Text
2022-06-03 06:23:011ST PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FPC 607.2 - THE DETAIL FOR HOT WATER SUPPLY
 STATES "100 FEET TO THE FARTHEST FIXTURE" AND IT IS 50
 FEET MAXIMUM OR A CIRCULATING LINE IS REQUIRED. PLEASE
 DETAIL THE DISTANCE AND SUPPLY A RECIRCULATING LINE IF
 REQUIRED.
  
 2. 2020 FEC C404.4 - THE MINIMUM PIPE INSULATION SHAL
 BE IN COMPLIANCE WITH TABLE C403.2.10, YOU HAVE LISTED
 TABLE 607.2.1 OF THE FPC. PLEASE CORRECT.
  
 3. 2017 WPB AMENDS 107.2.1 - YOUR SANITARY ISO HAS
 INCORRECTLY LABELED THE LAVATORY NEAR THE 3 COMP SINK
 (SHOULD BE HAND SINK) AND THE HAND SINK NEAR THE WC
 (SHOULD BE LAV).
  
 4. 2020 FPC - 607.1.1 - YOU HAVE LISTED A MIXING DEVICE
 FOR THE TEMPERED WATER AT THE PUBLIC LAV, BUT HAVE NOT
 LISTED A MXING DEVICE FOR "HOT WATER DELIVERY". PER
 607.1.1, THE THERMOSTAT ON THE WATER HEATER SHALL NOT
 BE THE LIMITING DEVICE FOR PROVIDING HOT WATER. PLEASE
 SHOW A DEVICE OTHER THAN THE THERMOSTAT ON THE WATER
 HEATER THAT LIMITS THE TEMPERATURE OF "HOT WATER". THIS
 IS IN ADDITION TO THE MIXING DEVICE FOR TEMPERED WATER
 AT THE LAV.
  
 5. 2020 FPC 708.1.3 - PLEASE DETAIL THE REQUIRED
 CLEANOUT AT THE JUNCTION OF THE BUILDING DRAIN AND THE
 SEWER. IF IT IS A WALKWAY OR TRAFFIC AREA, PLEASE SHOW
 THE DETAILS COMPLYING WITH 2020 FPC 708.1.10.2.
  
 6. 2020 FPC 708.1.1 - YOU DO NOT HAVE THE REQUIRED
 CLEANOUT ON THE HORIZONTAL BUILDING DRAIN WITHIN THE
 BUILDING.
  
 7. 2020 FPC 905.4 - THE VENT AT THE MOP SINK AND THE
 VENT AT THE WATER CLOSET ARE NOT ALLOWED TO BE
 HORIZONTAL UNTIL THEY ARE 6" ABOVE THE FIXTURE(S)
 SERVED. PLEASE RECONFIGURE AND SHOW A COMPLIANT VENTING
 SYSTEM.
  
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  