Date Text
2022-06-01 13:58:48PRIVATE PROVIDER MECHANICAL AUDIT
  
 1) THIS IS A CHANGE OF USE FROM WAREHOUSE TO RETAIL
 SPACE. WE DO NOT HAVE A RECORD OF ANY AIR CONDITIONING
 OF THIS SPACE EVER BEING PERMITTED. THESE UNITS WOULD
 NOT BE CONSIDERED EXISTING AND WILL BE LOOKED AT AS
 NEW.
  
 2) PROVIDE IN DETAIL THE PROCESS OR USE OF SPACE FOR
 THE PROCESSING AREA OF THIS RETAIL OCCUPANCY.
  
 3) I DO NOT SEE THE PRODUCT INFORMATION FOR THE ROASTER
 AS SUCH I CANNOT DO AN AUDIT ON THE INSTALLATION OF
 THIS ROASTER AT THIS TIME.
  
 4) THE SUBMITTAL STATES THAT THE VENTILATION OF THIS
 SPACE IS TO MEET FMC 402 FOR NATURAL VENTILATION AND
 THE OVERHEAD DOOR IS TO REMAIN OPEN ALL TIMES THE
 BUILDING IS OCCUPIED. PLEASE EXPLAIN HOW THE OUTDOOR
 AIR FOR THIS TENANT SPACE WILL BE ACHIEVED ON THE COLD
 DAYS OF WINTER AND THE HOT DAYS OF SUMMER WHEN THE
 DOORS WILL BE CLOSED TO HEAT AND COOL THE SPACE.
  
 5) THE ENERGY CALCULATIONS PRESENTED FOR THIS AUDIT
 CYCLE IS FOR AN OFFICE WITH A TOTAL SQUARE FOOTAGE OF
 1772. THERE IS AN OFFICE FOR THIS TENANT BUT THERE IS
 ALSO A RETAIL AREA WITH AN OPEN GARAGE DOOR AS WELL AS
 A PROCESSING AREA THAT ALSO HAS A ROLL UP GARAGE DOOR.
 PLEASE SHOW HOW WHEN THE ROLL UP DOORS ARE OPEN THIS
 WOULD MEET THE ENERGY CALCULATIONS.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  