Plan Review Notes
Plan Review Notes For Permit 21031236
Permit Number 21031236
Review Stop P
Sequence Number 1
Notes
Date Text
2021-08-25 16:57:2308/25/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE CITY OF WEST PALM BEACH HAS NO RECORD OF A
 CHANGE OF OCCUPANCY OR EXISTING SPACE ALTERATIONS.
 WOULD YOU PLEASE PROVIDE WHAT TYPE OF OCCUPANCY THIS
 INTERIOR BUILD-OUT WILL BE AND THE OCCUPANCY LOAD WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 2. PLEASE PROVIDE PLUMBING FIXTURE CALCULATIONS AND A
 SCHEDULE SHOWING THE REQUIRED AND PROVIDED FIXTURES IN
 COMPLIANCE WITH TABLE 403.3 FBC P.
  
 3. PROVIDE MINIMUM SANITARY FACILITIES ACCORDING TO
 2020 FBC P TABLE 403.1.
  
 4. WOULD YOU PLEASE GIVE THE LEVEL OF ALTERATION PER
 2020 FLORIDA EXISTING BUILDING CODE 301.1?
  
 5. PLEASE PROVIDE PLUMBING FIXTURE CALCULATIONS AND A
 SCHEDULE SHOWING THE REQUIRED AND PROVIDED FIXTURES IN
 COMPLIANCE WITH TABLE 403.3 FBC P.
  
 6. PLEASE PROVIDE THE STANDARD BEING USED FOR SIZING OF
 THE GREASE INTERCEPTOR. THE INTERCEPTOR SHALL BE SIZED
 IN ACCORDANCE WITH ONE OF THE STANDARDS LISTED IN 2020
 FBC SEC. P 1003.3.5 OR RULE 64E-6 OF THE FLORIDA
 ADMINISTRATIVE CODE AND THE CITY OF WEST PALM BEACH
 STANDARD DETAIL GS-7. A GREASE TRAP MAY BE REQUIRED,
 ALONG WITH SIZING. A SEPARATE PERMIT AND APPLICATION
 WILL BE NEEDED IF SO 2020 FBC P 1003.1.
  
 7. WOULD YOU PLEASE SHOW THE GREASE WASTE SEPARATION
 FROM TREATED WATER DISCHARGE TO THE SANITARY SYSTEM IN
 THE ISOMETRIC PER THE 2020 FBC SEC. P 1003.2 APPROVAL.
 8.
 9. IF THERE IS A GREASE INTERCEPTOR, PLEASE PROVIDE A
 CALCULATION. WOULD YOU PLEASE GIVE THE CAPACITY OF THE
 EXISTING INTERCEPTOR IN GALLONS?
  
 A. IS IT SHARED WITH OTHER RESTAURANTS, AND IF SO, WHAT
 IS THEIR VOLUME.
  
 B. IS IT A PASSIVE HYDRO-MECHANICAL - OR GRAVITY-TYPE
 GREASE INTERCEPTOR MADE OF CONCRETE STEEL OR
 FIBERGLASS?
  
 10. THE SERVICE SINK (MOP SINK) SURROUNDING THE WALL
 SHALL BE A NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE
 2017 FBC BUILDING SEC. 1210.2.2 AND 2017 FBC SEC. P
 310.3. WOULD YOU PLEASE MAKE A NOTE ON THIS SHEET?
  
 11. IN THE KITCHEN AREA, THERE IS A THREE-COMPARTMENT
 SINK. PLEASE PROVIDE DETAIL ON THE DRAINS TO AN
 INDIRECT WASTE INDEPENDENTLY FROM EACH OTHER PER THE
 2020 FBC SEC. P 802.1.1.
  
 12. HAND SINK SHALL NOT GO INTO GREASE INTERCEPTOR AS
 THEY DO NOT PRODUCE WASTE REQUIRING TREATMENT OR
 SEPARATION AND SHALL BE DISCHARGED INTO ANY INTERCEPTOR
 PER THE 2020 FBC SEC. 1003.2 APPROVAL.
  
 13. THERE IS NO CLEANOUT AT THE 4? CONNECTION OF THE
 BUILDING 2020 FBC P 708.1.3 BUILDING DRAIN AND BUILDING
 SEWER JUNCTION.
  
 14. HOT WATER DEVICE NOT SHOWN. PLEASE PROVIDE DETAIL
 AND SIZING FBC P 607.1.
  
 15. WOULD YOU PLEASE PROVIDE A PLUMBING PLAN INCLUDING
 A WATER ISOMETRIC DRAWING PER THE WPB AMEND TO FBC
 107.3.5.1.3(13)
  
 16. ON THE ISOMETRIC, PLEASE SHOW A TRAP PRIMER AND ITS
 SOURCE PER THE 2020 FBC SEC. 1002.4.1 TRAP SEAL
 PROTECTION.
  
 17. THE DESIGN COMPLIANCE MENTIONED THE FBC 2020, AND
 THERE IS ACCESSIBILITY AND PLUMBING. WOULD YOU PLEASE
 ADD THE ACCESSIBILITY AND PLUMBING AS WELL PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 18. THE RESTROOM REQUIRES ACCESSIBILITY DETAIL OF
 HEIGHTS AND DIMENSIONS, WHICH ARE NOT SHOWN. PLEASE
 PROVIDE DETAILED DRAWINGS FOR CLEAR FLOOR SPACE, GRAB
 BARS, WATER CLOSET, LAVS, ETC. PER THE 2020 FBC
 ACCESSIBILITY CODE.
  
 19. MINIMUM OF ONE STACK VENT OR VENT STACK EXTENDED TO
 THE OUTDOORS TO THE OPEN AIR PER THE 2020 FBC SEC. P
 918.7. SHOW COMPLIANCE WITH THE PLANS.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved