| 2021-08-25 17:16:48 | 08/25/21 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. WOULD YOU PLEASE PROVIDE THE CODE REFERENCE ON THE |
| | PLAN FOR THE GAS TYPE USING PER THE WPB AMENDMENTS TO |
| | FBC 102.3 APPLICATION OF REFERENCES? |
| | |
| | 2. WOULD YOU PLEASE SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE |
| | PER 2020 FBC FG SEC. 402.4.1, 402.4.2. |
| | |
| | 3. WOULD YOU PLEASE SHOW THE TYPE OF PIPE MATERIAL |
| | BEING INSTALLED, ALL PIPE SIZES, AND THE CORRESPONDING |
| | EHD NUMBER OF THE CORRUGATED STAINLESS-STEEL TUBING (IF |
| | APPLICABLE) FOR EACH PIPE SIZE PER THE WPB AMENDMENTS |
| | TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 4. WOULD YOU PLEASE GIVE THE TYPE OF GAS (LP OR |
| | NATURAL) PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 5. WOULD YOU PLEASE SHOW THE LOCATION OF ALL MP |
| | (STEP-DOWN) REGULATORS? A LISTED SHUTOFF VALVE SHALL BE |
| | INSTALLED IMMEDIATELY AHEAD OF EACH MP REGULATOR. 2020 |
| | FBC FG SEC. 409.4 OR 2020 FBC RES. SEC. G2420.4. |
| | |
| | 6. WOULD YOU PLEASE LIST THE BTU LOAD OF THE APPLIANCE |
| | ON THE SYSTEM? REFER TO THE 2020 FBC FG SECS. 401.8 |
| | THROUGH 402.6.1 AND TABLES 402.4 (1) THROUGH 402.4 |
| | (37). |
| | |
| | 7. WOULD YOU PLEASE SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY (GAS METER / MP REGULATOR / LP TANK) TO THE |
| | MOST REMOTE OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | THE 2020 FBC FG SEC. 402.4.1. |
| | |
| | 8. WOULD YOU PLEASE INDICATE THE SYSTEM'S DELIVERY |
| | PRESSURE (PSI) ON THE PLAN PER THE 2020 FBC FG SEC. |
| | 402.2. |
| | |
| | 9. WOULD YOU PLEASE SUBMIT THE MANUFACTURER'S |
| | SPECIFICATION SHEETS/INSTALLATION MANUAL FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH 2020 FBC FG SEC. |
| | 305.1. |
| | |
| | 10. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE |
| | INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT |
| | SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE 2020 |
| | FBC FG SECS. 402.2 AND 301.3. |
| | |
| | 11. WOULD YOU PLEASE PLACE A NOTE ON BOTH SETS OF PLANS |
| | LISTING THE SIZING TABLES FROM GAS CODES OR ANOTHER |
| | STANDARD USED IN THIS SYSTEM'S DESIGN PER THE 2020 FBC |
| | FG SEC. 402.3. |
| | |
| | 12. WOULD YOU PLEASE SHOW ALL UNIONS IN FRONT OF |
| | REGULATOR 1 FOOT OF EITHER SIDE PER THE 2020 FBC FG SEC |
| | 410.2? |
| | |
| | 13. WOULD YOU PLEASE LABEL THE SHUT-OFF, AND THEY SHALL |
| | BE ACCESSIBLE WITHOUT MOVING THE EQUIPMENT PER THE 2020 |
| | FBC SEC. G2403 (202) GD, ACCESS. |
| | |
| | 14. WOULD YOU PLEASE LABEL AND SHOW DRIP LEG ON |
| | EQUIPMENT PER THE 2020 FBC FG 408.2. |
| | |
| | 15. WOULD YOU PLEASE SHOW THE EMERGENCY HOOD SHUT DOWN |
| | SHUTOFF VALVE THAT SHALL BE BELOW THE CEILING? THE |
| | MANUAL SHUTOFF VALVE SHALL BE UPSTREAM. UNION TO BE |
| | DOWNSTREAM OF MANUAL VALVE. SECS. 10.4, 10.5 OF NFPA |
| | 96-08. |
| | |
| | NOTE: YOU MAY CHOOSE TO HAVE A GAS REVIEW DONE THIS |
| | TIME AND ADDRESS THE COMMENTS ABOVE. THIS WILL HAVE THE |
| | GAS APPROVE FOR A SUB PERMIT, OR IF YOU DECIDED NOT TO |
| | ADDRESS THESE COMMENTS, PLEASE PUT A NOTE ON THE GAS |
| | HEATER (A SEPARATE PERMIT BY A LICENSED CONTRACTOR FOR |
| | THE GAS SYSTEM). THEN PLEASE TAKE OFF ANY GAS SHOWN ON |
| | PLANS; THESE COMMENTS CAN BE FORWARD TO THE GAS |
| | CONTRACTOR FOR REFERENCE. AN N WILL BE PUT ON THIS |
| | REVIEW, WHICH STANDS FOR NOT REQUIRED, BUT A SUB PERMIT |
| | WON'T BE ISSUED ONCE A REVIEW IS DONE FOR THAT SUB |
| | PERMIT, SO PLEASE BE ADVISED ON THIS PROCEDURE. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |